18
|
Commissioning
Main menu item
Sub-menu item 1 Sub-menu item 2 Explanations
→ Free cooling Free cool active: No
Outd. temp
activation
22°C
Set free cooling active toYes or No.
Set the lower outdoor day
temperature limit for the activation
of the free cooling function. The
temperature of the previous day
needs to be over the set
temperature in order activate the
free cooling function.
Outd. temp night
High: 15.0°C
Low: 5.0°C
Room temp min. 18°C
Set the upper outdoor night
temperature limit for the activation
of the free cooling function.
Set the lower outdoor night
temperature limit for the activation
of the free cooling function.
Set the lower room temperature
limit. The temperature needs to be
above this value for the free
cooling function to stay active.
If no room sensor are connected
extract air is valid.
Hour for start/stop
Free cooling
Start: 0
Stop: 7
Set the start and stop time for the
free cooling function
For example Start: 0 and
Stop: 6
means that the free cooling
sequence is active between 00.00
and 06.00 h.
Time to block heat
output after Free
cooling
60 min
Set the delay in minutes from the
time where the free cooling
sequence has stopped until a
possible heating sequence is
initiated, i.e. how long a cooler
room temperature than set
temperature can be accepted
Fan setpoint offset
when free cooling
SAF: 0 %
EAF: 0 %
Set the fan speed in percentage of
the normal speed for each fan
individually during the free cooling
sequence
Outdoor sensor
placed in intake
channel (intake duct)
No
Set if the outdoor sensor is placed
in the intake duct or not.
Choose between No and Yes
Preset is No.
→ Support control Support control
Active: No
EAF running during
Support contr.: Yes
When using the control function
room control or extract air
temperature control, it is possible
to utilize support-heating and/or
support-cooling. Minimum running
time is settable 0…720 minutes
(factory setting 60 minutes).
Choose between “Active: Yes or
No”.
(For start and stop temperatures
see the "Temperature" menu)
Min. run time for
support ctrl: 60 min
Set the minimum running time in
minutes for support control