Supplementary instructions for UVR61-3
Building drying with ventilator
A special application of the universal controller is the energy-saving and cost-effective drying of
basements and other building parts with fan control. The special functionality (measurement of the
absolute humidity) of the sensor RFS-DL enables this simple drying out of buildings in connection with
the universal controller. The absolute humidity inside and outside is compared and a fan switched on
or off accordingly.
Building drying can be carried out with all universal controllers that have a DL bus (with the excep-
tion of UVR63-H).
Goal
Lowering humidity through specific ventilation with dry air
Improvement of air quality and odour with regular ventilation
Replacement of energy-intensive dehumidification devices
Required material:
Complete UVR61-GT set comprising:
1 universal controller
01/UVR61-3-R
2 humidity sensors
01/RFS-DL
The address must be changed if the RFS-DL is
installed outside.
The DIP switch 1 must be set to ON.
This changes the sensor address to 2.