32
Alarm code is shown as “34” and
battery led blinking
Battery voltage is too low or
the charger is fault.
Contact your dealer.
Alarm code is shown as “32” and
INV or BYPASS led blinking.
UPS is overload
Remove excess loads from
UPS output.
Alarm code is shown as “29” and
FAULT led light.
The UPS shut down
automatically because short
circuit occurs on the UPS
output.
Check output wiring and if
connected devices are in
short circuit status.
Alarm code is shown as “9” and
FAULT led light.
Fan fault.
Contact your dealer.
Alarm code is shown as “01,02,
15,16,17,18”
A UPS internal fault has
occurred.
Contact your dealer.
Battery backup time is
shorter than nominal value
Batteries are not fully
charged
Charge the batteries for at
least 5 hours and then check
capacity. If the problem still
persists, consult your dealer.
Batteries defect
Contact your dealer to
replace the battery.