ADJUST MENU
Item Field
Range
Access Description
60 to 220°F
(15.5 to 104.5°C)
Default = 180°F
(82.0°C)
Ad
SETPOINT OCCUPIED
SECTION J
The minimum boiler target temperature when a
setpoint demand is present during the Wake and
Occupied periods.
Note: This item is only available when Setpoint Mode
is set 1 through 4.
OFF, ON
Default = OFF
Ad
SETPOINT UNOCCUPIED SECTION J
Selects whether or not a Setpoint demand will be
responded to during the Sleep and Unoccupied
periods.
Note: This item is only available when Setpoint Mode
is set 1 through 4 and a network setback schedule
is selected.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 70°F (21.0°C)
InS
Ad
WWSD OCCUPIED SECTION B
The system’s warm weather shut down temperature
during the Wake and Occupied periods.
40 to 100°F, OFF
(4.5 to 38.0°C, OFF)
Default = 60°F (15.5°C)
Ad
WWSD UNOCCUPIED SECTION B
The system’s warm weather shut down temperature
during the Sleep and Unoccupied period.
Note: This item is only available when the Schedule
is not set to OFF.
Adjust Menu (5 of 5)
After the last item, the control returns to the first item in the menu.

Other manuals for Tekmar Universal Reset Module 422

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tekmar Universal Reset Module 422 and is the answer not in the manual?

Tekmar Universal Reset Module 422 Specifications

General IconGeneral
BrandTekmar
ModelUniversal Reset Module 422
CategoryControl Unit
LanguageEnglish

Related product manuals