7 of 32 © 2007 D 422 - 08/07
Item Field Range Access Description
– – –, 35 to 230°F
(– – –, 1.5 to 110.0°C)
Ad
BOILER TARGET
SECTION C
The boiler target is the temperature the control is currently
trying to maintain at the boiler supply sensor. “– – –” is
displayed when no heat is required for boiler zones.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
-22 to 266°F
(-30.0 to 130.0°C)
InS
Ad
BOILER RETURN SECTION G
Current boiler return water temperature as measured
by the boiler sensor.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Ret.
0-100% Ad
BOILER MODULATION SECTION C
Current percent modulation of the boiler’s burner.
Note: This item is only available when the Boiler
On-Off / Mod DIP switch is set to Mod, and the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
0 to 9999 hr
InS
Ad
BOILER
The total running time of the boiler since this item
was last cleared. To clear this item, press the Up
and Down buttons simultaneously while viewing
this item.
Note: This item is only available when the Boiler
Sensor Sup / Ret DIP switch is set to Sup.
View Menu (2 of 2)
After the last item, the control returns to the first item in the menu.
VIEW MENU

Other manuals for Tekmar Universal Reset Module 422

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Tekmar Universal Reset Module 422 and is the answer not in the manual?

Tekmar Universal Reset Module 422 Specifications

General IconGeneral
BrandTekmar
ModelUniversal Reset Module 422
CategoryControl Unit
LanguageEnglish

Related product manuals