Page #13 background imageLoading...
Page #13 background image
TOPVERT S1 Series
E-
12
Pr0-22
Waiting time to restart
after stop
0.00~60.00sec
0.00
0 Fan on while power on
Bit0
1 Fan on while run command effect
0
Bit1
1
(Factory Reserved)
0
Bit2
1
(Factory Reserved)
0 PID reverse operation allow
Bit3
1
PID reverse operation not allow
0
Pr0-23
Cooling fan control & PID
direction
Bit4
1
(Factory Reserved)
b00000
0=0.01 Hz
1=0.10Hz
2=1.00Hz
Pr0-24 Resolution of dial
3=10.00 Hz
1
0: Team A
1: Team B
Pr0-25 Parameter select
2: (Factory Reserved)
0
Group 1: Basic parameters
Parame
ters
Functions Settings
Factory
Setting
User
Pr1-00
Maximum operation frequency
50.00600.00Hz 60.00/50.00
Pr1-01
1st Frequency 1 (Fbase 1)
(Base frequency 1 )
0.00600.00 Hz 60.00/50.00
Pr1-02
1st Voltage 1 (Vbase 1)
(Motor rated voltage 1)
230V models:
0.0255.0V
460V models:
0.0510.0V
230V:230.0
460V:460.0
Pr1-03
2nd Frequency 1 (Fmid 1)
(Middle frequency 1)
0.00600.00 Hz
0.50
Pr1-04
2nd Voltage 1 (Vmid 1)
(Middle voltage 1)
230V models:
0.0255.0V
460V models:
0.0510.0V
230V:5.0
460V:10.0
Pr1-05
3rd Frequency 1 (Flow 1)
(Low-point frequency 1)
0.00600.00 Hz 0.50
Pr1-06
3rd Voltage 1 (Vlow 1)
(Low-point voltage 1)
230V models:
0.0255.0
460V models:
0.0510.0V
230V:5.0
460V:10.0
Pr1-07
0Hz Voltage 1 (V0Hz 1)
(Output voltage at 0Hz)
230V models:
0.025.5
460V models:
0.051.0V
0.0
Pr1-08
Start-up frequency
0.00600.00 Hz
0.50
Pr1-09 Output frequency Upper limit
0.0150.0% of Maximum operation
frequency (Pr1-00)
110.0
Pr1-10
Output Frequency Lowerl limit
0.0100.0% of Maximum operation
frequency (Pr1-00)
0.0
Pr1-11
1
st
Acceleration time
0.0060000 Sec 10.00/60.00
Pr1-12
1
st
Deceleration time
0.0060000 Sec 10.00/60.00
Pr1-13
2
nd
Acceleration time
0.0060000 Sec 10.00/60.00
Pr1-14
2
nd
Deceleration time
0.0060000 Sec 10.00/60.00
Pr1-15
(Factory Reserved) (Factory Reserved)
Pr1-16
(Factory Reserved)
(Factory Reserved)
Pr1-17
(Factory Reserved)
(Factory Reserved)
Pr1-18
1st/2nd
Acceleration/Deceleration
Switching frequency
0.00600.00 Hz 0.000
Pr1-19
S-Acc. departure time when
accelerate
0.0012000 Sec 0.00