EasyManuals Logo

Toshiba R410A User Manual

Toshiba R410A
228 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #71 background imageLoading...
Page #71 background image
71
7. APPLIED CONTROL
7-1. Indoor Unit
7-1-1. Setup of Selecting Function in Indoor Unit
(Be sure to Execute Setup by a Wired Remote Controller)
<Procedure> Execute the setup operation while the unit stops.
1
Push
SET
,
CL
, and
TEST
buttons simultaneously for 4 seconds or more.
The firstly displayed unit No. indicates the master indoor unit address in the group control.
In this time, the fan of the selected indoor unit is turned on.
2
Every pushing
UNIT
button, the indoor unit numbers in the group control are successively
displayed. In this time, the fan of the selected indoor unit only is turned on.
3
Specify the item code (DN) using the setup temperature and buttons.
4
Select the setup data using the timer time and buttons.
(When selecting the DN code to 33, change the temperature indication of the unit from “°C
to “°F” on the remote controller.)
5
Push
SET
button. (OK if display goes on.)
To change the selected indoor unit, return to procedure
2
.
To change the item to be set up, return to procedure
3
.
6
Pushing
TEST
button returns the status to normal stop status.
6
3
5
2
4
1
ON / OFF
FAN
TEMP.
SWING/FIXTIME
MODE
VENT
UNITSET CL
FILTER
RESET
TEST
TIMER SET