EasyManuals Logo
Home>Toshiba>Recording Equipment>TCS-NET

Toshiba TCS-NET User Manual

Toshiba TCS-NET
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
TCS-NET General Purpose Interface
Service Manual
8
Toshiba
The PCB layout is shown below. Checkpoints are circled.
4-2. An air conditioner indoor unit connected to the RO1
and DI3 relay contacts using the HA connector cannot
be operated from the central remote controller
An air
conditioning
operation
connected to the
RO1 relay contact
is not available
from the central
remote controller
NO
See the Installation Manual,
and make the settings
correctly.
NO
See the Installation Manual,
and make the connection
correctly.
YES
Is the relay mode set correctly
(SW5)?
SW5-2 and SW5-4 = OFF;
SW5-3 = ON
Are DI3/RO1 and the air
conditioner HA connector
connected correctly?
See the chapter titled "WIRING"
of the Installation Manual.
+00DE89308801_01EN_SVM_General_IF.book Page 8 Tuesday, January 20, 2009 6:44 PM

Other manuals for Toshiba TCS-NET

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TCS-NET and is the answer not in the manual?

Toshiba TCS-NET Specifications

General IconGeneral
BrandToshiba
ModelTCS-NET
CategoryRecording Equipment
LanguageEnglish

Related product manuals