AIC, Fuse and Wire sizes
Use the UL listed fuses at connecting to power supply.
Short circuit test is performed under the condition of the power supply short-circuit currents in below.
These interrupting capacities and fuse rating currents depend on the applicable motor capacities.
Table 3 AIC, Fuses and Wire sizes
Inverter model
Voltage
(V)
Input
withstand
rating (kA)
Output
Interrupt
rating (kA)
Branch circuit
protection
Rating
(A)
Cable sizes of
power circuit
Earth Cable
Marking Y (1) X (2) Z1 Z2
- -
VFS15-4004PL1
480 5 5 Class CC 6 AWG 14 AWG 14
VFS15-4007PL1
480 5 5 Class CC 6 AWG 14 AWG 14
VFS15-4015PL1
480 5 5 Class CC 12
AWG 14 AWG 14
VFS15-4022PL1
480 5 5 Class J 15
AWG 14 AWG 14
VFS15-4037PL1
480 5 5 Class J 25
AWG 12 AWG 14
Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kilo
Amperes,___Y___Volts maximum, when protected by___Z1___with a maximum rating of___Z2___.
(1) Input withstand rating is that for which the product has been designed thermally. Installation on a
supply greater than this level will require additional inductance to satisfy this level.
(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide
branch circuit protection. Branch circuit protection must be provided in accordance with the National
Electrical Code and any additional local codes. This is dependant on the type of installation.
In case of using with a higher AIC capability up to 100kA(*1), the Short Circuit Current Ratings (SCCR)
become 100kA(*1) by installing with the circuit breakers(GV•P) or the fuses listed in Table 4.
Table 4 AIC 100kA, Fuses, Circuit breakers and Wire sizes
Inverter model
Voltage
(V)
Branch circuit protection
Cable sizes of
power circuit
Earth Cable
With Fuses With circuit breakers
Class (*2)
Rating
(A)
Type-
Form
(*3)
Setting
(A)
VFS15-4004PL1
480 Class J
6 GV2P07
9 AWG 14 AWG 14
VFS15-4007PL1
480 Class J
6 GV2P08
9 AWG 14 AWG 14
VFS15-4015PL1
480 Class J
15 GV2P10
9 AWG 14 AWG 14
VFS15-4022PL1
480 Class J
15 GV2P14
10 AWG 14 AWG 14
VFS15-4037PL1
480 Class J
25 GV3P13
13 AWG 12 AWG 14
(*1) In case with the circuit breaker, the Short Circuit Current Ratings (SCCR) is 65kA.
(*2) The manufacturer of the fuses should be "Cooper Bussmann" or "Mersen" (formerly, "Ferraz
Shawmut") for the compliance of UL standard.
(*3) The manufacturer of the listed circuit breaker is "Schneider Electric".

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals