E6582185
6
6.18 PWM carrier frequency
Load reduction (current reduction) by carrier frequency, ambient temperature and input voltage
VFS15-
Ambient
temperature
Input voltage 480V or less Input voltage above 480V
PWM carrier frequency [kHz] PWM carrier frequency [kHz]
2.0~4.0 4.1~12.0
12.1~16.0 2.0~4.0 4.1~12.0
12.1~16.0
4004PL1-W1
40
°
C or less
1.5 A 1.5 A 1.5 A
1.5A 1.5A 1.2A
Above 40
50
°
C
1.5 A 1.5 A 1.5 A
1.5A 1.5A 1.2A
Above 50
60
°
C
1.4 A 1.2 A 1.2 A
1.4A 1.2A 1.0A
4007PL1-W1
40
°
C or less
2.3 A 2.1 A 2.1 A
2.1A 1.9A 1.9A
Above 40
50
°
C
2.3 A 2.1 A 2.1 A
2.1A 1.9A 1.9A
Above 50
60
°
C
2.2 A 1.7 A 1.7 A
2.0A 1.5A 1.5A
4015PL1-W1
40
°
C or less
4.1 A 3.7 A 3.3 A
3.8A 3.4A 3.1A
Above 40
50
°
C
4.1 A 3.7 A 3.3 A
3.8A 3.4A 2.6A
Above 50
60
°
C
3.9 A 3.0 A 2.6 A
3.6A 2.5A 1.5A
4022PL1-W1
40
°
C or less
5.5 A 5.0 A 4.5 A
5.1A 4.6A 4.2A
Above 40
50
°
C
5.5 A 5.0 A 4.5 A
5.1A 4.6A 4.2A
Above 50
60
°
C
5.2 A 4.0 A 3.6 A
4.8A 3.7A 3.4A
4037PL1-W1
40
°
C or less
9.5 A 8.6 A 7.5 A
8.7A 7.9A 6.9A
Above 40
50
°
C
9.5 A 8.6 A 7.5 A
8.7A 7.9A 5.5A
Above 50
60
°
C
9.0 A 6.9 A 6.0 A
8.3A 5.6A 3.3A
9.1.2 Measures to satisfy the EMC Directive
Combination of inverter and filter
Inverter type
Conducted noise
IEC61800-3, category C2
(Motor wiring length of 5m or less)
Conducted noise
IEC61800-3, category C1
(Motor wiring length of 20m
or less)
Conducted noise
IEC61800-3, category C2
(
Motor wiring length of 50m
or less)
VF S15-4004PL1-W1
Built-in filter
EMFS11-4015BZ
VF S15-4007PL1-W1 EMFS11-4015BZ
VF S15-4015PL1-W1 EMFS11-4015BZ
VF S15-4022PL1-W1 EMFS11-4025CZ
VF S15-4037PL1-W1 EMFS11-4025CZ
11.4 Default settings by inverter rating
Default settings
The default setting of motor parameters are adapted to Toshiba IE3 motor.
In case of using Toshiba standard IE1 motor, the parameters values should be adjusted according to Table 4
(VFS15-4004PL to 4037PL) in E6582165 (VF-S15 motor control parameter default setting update information).
Inverter type
Torque
boost
value
Dynamic
braking
resistance
Dynamic
braking
resistor
capacity
Automatic
torque
boost
value
Motor
rated
capacity
*1
Motor
rated
current
Motor
no-load
current
Over-
voltage
stall
protection
level
Integrating
wattmeter
display unit
selection








 
VFS15-
(%) () (kW) (%) (kW) (A) (%) (%)
4004PL1-W1
6.0 200.0 0.12 6.2 0.40 1.0 65 141 0
4007PL1-W1
4.8 200.0 0.12 4.3 0.75 1.7 55 141 0
4015PL1-W1
4.8 200.0 0.12 4.4 1.50 3.2 42 141 0
4022PL1-W1
3.1 200.0 0.12 2.9 2.20 4.7 50 141 0
4037PL1-W1
3.1 160.0 0.12 2.8 4.00 7.3 38 141 1
*1: When region setting is JP,  is set to 3.7(kW).
If the parameters and the adjustment range, which are not shown in the manuals (E6581611 and additional
sheet), are displayed in the inverter, those parameters and adjustment range are “the factory specific
coefficient parameters”. Do not change or set the value of these parameters and adjustment range.

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals