E6582185
5
2) Grounding capacitor switch
Three-phase 500V model have a built-in high-attenuation noise filter and is grounded via a capacitor.
A switch screw makes for easy switching to reduce leakage current from the inverter and the load on the
capacitor. However, be careful, as reducing the load means non-conformity with the EMC standard on
the inverter itself. Always do switching with the power off.
Note 1) Figure is VFS15-4022PL1-W1 to 4037PL1-W1.
1.4.4 Installation
Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC
to AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Voltage class
Inverter type
Calorific values (W)
Note 1)
Amount of forcible air
cooling ventilation
required (m
3
/min)
Heat discharge
surface area
required for sealed
storage cabinet (m
3
)
Standby
power
requirement
(W)
Note 2)
4kHz 12kHz 4kHz 12kHz 4kHz 12kHz
Three-phase
500V class
VFS15-
4004PL1-W1
29 39 0.17 0.22 0.59 0.79 17
4007PL1-W1
40 54 0.23 0.30 0.79 1.07 17
4015PL1-W1
62 88 0.35 0.50 1.24 1.76 17
4022PL1-W1
77 108 0.44 0.61 1.54 2.16 19
4037PL1-W1
113 169 0.64 0.96 2.26 3.38 19
Note 1) Case of 100% Load Continuation operation. The heat loss for the optional external devices
(input AC reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table
Note 2) It is power consumption when power is on but is not output (0Hz), and cooling fan is activated (model
with cooling fan).
Install the screw at grounding capacitor switch position A ( ), th
e
grounding capacitor's capacity from small to large. (Default setting)
Tightening torque 0.5 Nm (4.4 lbin)
Move the screw to grounding capacitor switch position B ( ),
the
grounding capacitor's capacity from large to small. This reduce
s the
leakage current.
When this inverter is connected
to the IT system (insulated ground
of power supply or the system has Impedance), the screw
has to be
move
d as the figure shows.
Grounding
capacitor
switch
position
A ( )
Grounding
capacitor
switch
position
B (
)

Other manuals for Toshiba TOSVERT VF-S15 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Toshiba TOSVERT VF-S15 series and is the answer not in the manual?

Toshiba TOSVERT VF-S15 series Specifications

General IconGeneral
BrandToshiba
ModelTOSVERT VF-S15 series
CategoryInverter
LanguageEnglish

Related product manuals