18-AC95D1-1 21
STEP 8 - Verify typical performance.
Refer to System Pressure Curves in the Service
Facts to verify typical performance.
STEP 6 - Adjust refrigerant level to attain
proper gage pressure.
Add refrigerant if the Liquid Gage Pressure
is lower than the chart value.
1. Connect gages to refrigerant bottle
and unit as illustrated.
2. Purge all hoses.
3. Open bottle.
4. Stop adding refrigerant when liquid
line temperature and Liquid Gage
Pressure matches the charging chart
Final Subcooling value.
Recover refrigerant if the Liquid Gage Pres-
sure is higher than the chart value.
20 MIN.
STEP 7 - Stabilize the system.
1. Wait 20 minutes for the system condi-
tion to stabilize between adjustments.
Note: When the Liquid Line Temperature and
Gage Pressure approximately match the chart,
the system is properly charged.
2. Remove gages.
3. Replace service port caps to prevent
leaks. Tighten finger tight plus an ad-
ditional 1/6 turn.
(Example only - see Service Facts)
PRESSURE CURVES FOR 4TTX6060E
EGATS DNOCESEGATS TSRIF
1A66F3EET41A66F3EET4
Cooling with Thermal Expansion Valve Cooling with Thermal Expansion Valve
LIQUID PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
ION PRESSURE (PSIG)
OUTDOOR TEMPERATURE (Degree F)
COOLING PERFORMANCE CAN BE CHECKED WHEN THE OUTDOOR TEMP IS ABOVE 65 DEG F.
TO CHECK COOLING PERFORMANCE, SELECT THE PROPER INDOOR CFM, ALLOW PRESSURES TO STABILIZE. MEASURE INDOOR WET BULB
TEMPERATURE, OUTDOOR TEMPERATURE, LIQUID AND SUCTION PRESSURES. ON THE PLOTS LOCATE OUTDOOR TEMPERATURE (1);
LOCATE INDOOR WET BULB (2); FIND INTERSECTION OF OD TEMP. & ID W.B. (3); READ LIQUID (4) OR SUCTION (5) PRESSURE IN LEFT COLUMN .
EGATS DNOCES :ELPMAXEEGATS TSRIF :ELPMAXE
.F 28 .PMET ROODTUO )1( .F 28 .PMET ROODTUO )1(
.F 76 BLUB TEW ROODNI )2( .F 76 BLUB TEW ROODNI )2(
NOITCESRETNI TA )3( NOITCESRETNI TA )3(
(4) LIQUID PRESSURE @ 1210 CFM IS 306 PSIG (4) LIQUID PRESSURE @ 1570 CFM IS 288 PSIG
(5) SUCTION PRESSURE @ 1210 CFM IS 139 PSI
(5) SUCTION PRESSURE @ 1570 CFM IS 144 PSI
INTERCONNECTING LINES ACTUAL:
GAS - 1 1/8" O.D. LIQUID PRESSURE SHOULD BE +/- 10 PSI OF CHART
LIQUID - 3/8" O.D. SUCTION PRESSURE SHOULD BE +/- 3 PSIG OF CHART
DWG.NO. 4TTX6060E1
110
120
130
140
150
160
170
180
40 50 60 70 80 90 100 110 120
110
120
130
140
150
160
170
180
40 50 60 70 80 90 100 110 120
200
250
300
350
400
450
500
40 50 60 70 80 90 100 110 120
200
250
300
350
400
450
500
40 50 60 70 80 90 100 110 120
(1)
(3)
(3)
(5)
(4)
(2)
(2)
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM 71,
67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM 71,
67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM 71,
67, 63 AND 59 DEG F.
INDOOR ENTERING
WET BULB CURVES
TOP TO BOTTOM 71,
67, 63 AND 59 DEG F.
(2)
(1)
(4) (3)
(2)
(3)
(5)