EasyManuals Logo
Home>Trane>Heat Pump>4TWB3042B

Trane 4TWB3042B User Manual

Trane 4TWB3042B
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
20 18-BC85D1-2
STEP 1 - Check the outdoor temperatures.
Subcooling (in cooling mode) is the only recom-
mended method of charging above 55º F ambi-
ent outdoor temperature. See Section 14.2.
For outdoor temperatures below 55º F, see Sec-
tion 14.3.
Note: It is important to return in the spring or
summer to accurately charge the system in the
cooling mode when outdoor ambient tempera-
ture is above 55º F.
For best results the indoor temperature should
be kept between 70º F to 80º F.
Section 14. System Charge Adjustment
14.1 Temperature Measurements
14.2 Subcooling Charging in Cooling (Above 55º F Outdoor Temp.)
Indoor Temp
80º F
70º F
Outdoor Temp 1
55º F
120º F
Outdoor Temp 2
See Section 14.3 for
Outdoor
Temperatures
Below 55º F
See Section 14.2 for
Outdoor
Temperatures
Above 55º F
55º F
STEP 1 - Use the refrigerant line total length
and lift measurements from Section 5.3.
Total Line Length = __________ Ft.
Vertical Change (Lift) = __________ Ft.
LIFT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane 4TWB3042B and is the answer not in the manual?

Trane 4TWB3042B Specifications

General IconGeneral
BrandTrane
Model4TWB3042B
CategoryHeat Pump
LanguageEnglish

Related product manuals