Product Specification
Model 4WCZ6036*3 4WCZ6048*3 4WCZ6060*3 4WCZ6036*4 4WCZ6048*4 4WCZ6060*4
RATED Volts/PH/Hz 208-230/3/60 460/3/60
Performance Cooling BTUH
(a)
36000 47500 57000 36000 47500 57000
Indoor Airflow (CFM)
28800 1575 1780 1125 1575 1780
Power Input (KW)
LOCATED ON UNIT NAMEPLATE
EERH/L/SEER BTU/Watt-Hr
(b)
11/16/16 12.2/ 17.45/16 11.5/ 15.9/15 12.2/ 17.5/16 12/ 17.5/16 11.5/ 15.9/15
Sound Power Rating [dB(A)]
(c)
70 72 74 70 72 74
PERFORMANCE HEATING
(High Temp.) BTUH (High/
Low)
31000 /22400 42000 /31200 53500 /37000 31000/ 22400 42000/ 31200 53500/ 37000
Power Input (KW)
LOCATED ON UNIT NAMEPLATE
(Low Temp.) BTUH (High/
Low)
19200 /12000 23200 /17000 34000/19000 19200 /12000 23200 /17000 34000 /19000
Power Input (KW)
LOCATED ON UNIT NAMEPLATE
HSPF (BTUH/Watt-Hr)
8.3 8.5 8.3 8.3 8.5 8.3
POWER CONN. — V/Ph/Hz 208-230/3/60 460/3/60
Min. Brch. Cir. Ampacity
(d)
LOCATED ON UNIT NAMEPLATE
Fuse Size — Max. (amps)
LOCATED ON UNIT NAMEPLATE
Fuse Size — Recmd. (amps)
LOCATED ON UNIT NAMEPLATE
COMPRESSOR 2 STAGE SCROLL
VOLTS/PH/HZ 208-230/3/60 460/3/60
R.L. Amps — L.R. Amps
LOCATED ON UNIT NAMEPLATE
OUTDOOR COIL — TYPE SPINE FIN
Rows/F.P.I 2 / 24
Face Area (sq. ft.)
15.49 23.57 15.49 23.57
Tube Size (in.)
3/8
Refrigerant Control
EXPANSION VALVE
INDOOR COIL — TYPE PLATE FIN
Rows/F.P.I 4/15
Face Area (sq. ft.)
3.5 5.0 3.54 5.0
Tube Size (in.)
3/8
Refrigeration Control
EXPANSION VALVE
Drain Conn. Size (in.)
3/4 FEMALE NPT
OUTDOOR FAN — TYPE PROPELLER
DIA. (IN.)
23.4 28.2 23.4 28.2
DRIVE/NO. SPEEDS DIRECT / 1
CFM @ 0.0 in. w.g.
(e)
3020 4220 4700 3020 4220 4700
Motor — HP/R.P.M 1/6 /830 1/4 /830 1/6 /830 1/4 /830
Volts/Ph/Hz 208-230/1/60 460/1/60 208–230/1/60
F.L. Amps/L.R Amps
LOCATED ON UNIT NAMEPLATE
INDOOR FAN — TYPE CENTRIFUGAL
Dia. x Width (in.)
10x10 11x10 10x10 11x10
Drive/No. Speeds
DIRECT / VARIABLE
CFM @ 0.0 in. w.g.
(f)
SEE FAN PERFORMANCE TABLE
Motor — HP / R.P.M. 3/4 /VARIABLE 1/VARIABLE 1/2 / VARIABLE 3/4 / VARIABLE 1 / VARIABLE
Volts/Ph/Hz 208–230/1/60 460/1/60 230/1/60
F.L. Amps
LOCATED ON UNIT NAMEPLATE
FILTER / FURNISHED
NO
Type Recommended
THROWAWAY
Recmd. Face Area (sq. ft)
(g)
4.0 5.3 4.0 5.3
REFRIGERANT R-410A
Charge (lbs.)
LOCATED ON UNIT NAMEPLATE
Subcooling
8° F 10° F 8° F 10° F
(a)
Rated in accordance with AHRI Standard 210/240.
(b)
Rated in accordance with D.O.E. test procedure.
(c)
Sound Power values are not adjusted for AHRI 270–95 tonal corrections.
(d)
Calculated in accordance with currently prevailing Nat’l Electrical Code.
(e)
Standard Air — Dry Coil — Outdoor.
(f)
Standard Air — Dry Coil — Indoor
(g)
Filters must be installed in return air stream. Square footages listed are based on 300 f.p.m. face velocity. If permanent filters are used size per
manufacturer’s recommendation with a clean resistance of 0.05” W.C.