Model CVGF Water Connection Pipe Size
Shell Size
500 700 1000
Water Passes Metric Pipe Size (mm) DN
Evaporator
2 Pass DN 200 (8”) DN 250 (10”) DN 300 (12”)
3 Pass DN 200 (8”) DN 200 (8”) DN 250 (10”)
Condenser
Condenser DN 250 (10”) DN 300 (12”) DN 350 (14”)
23
Evaporator Water Box Length — SI (I-P)
Length
No. mm (in)
Shell Pressure Evap. Passes Supply Return
500
10 bar (150 psig) NMAR 2 402 (15.82) 226 (8.89)
10 bar (150 psig) NMAR 3 402 (15.82) 402 (15.82)
700
10 bar (150 psig) NMAR 2 489 (19.25) 235 (9.25)
10 bar (150 psig) NMAR 3 438 (17.24) 438 (17.24)
1000
10 bar (150 psig) NMAR 2 581 (22.87) 276 (10.87)
10 bar (150 psig) NMAR 3 530 (20.87) 530 (20.87)
Condenser Water Box Length — SI (I-P)
Length
No. mm (in)
Shell Pressure Evap. Passes Supply Return
500 10 bar (150 psig) NMAR 2 486 (19.02) 204 (8.03)
700 10 bar (150 psig) NMAR 2 582 (22.87) 231 (9.09)
1000 10 bar (150 psig) NMAR 2 658 (25.75) 276 (10.87)
Physical Dimensions
CTV-PRC001-E4