RT-SVX36G-EN 99
Unit Start Up
Set Drain Duration Timer
Enter service test mode from unit Human Interface. Navigate to the compressor condenser fan
submenu. Under head pressure control, use manual control.
Close drain valve and energize water inlet solenoid valve until water reaches nominal level. Once
level is achieved, de-energize fill solenoid. Open drain valve and time how long it takes for the water
level to drop one inch, make sure to take into account the closing time of the valve.
Figure 45. Actuator shaft adapter removal/assembly
Figure 46. Actuator is shipped in “drain during power loss” configuration
Locking clip
Shaft adapter
1
2
To drain during power loss,
set shaft adapter to 0 degrees
To hold during power loss,
set shaft adapter to 90 degrees