General information
Table 2 - General data - RTCA
Unit size 108 109 111 113 115 116
Condenser
Condenser type Aluminium fins/copper tubes
Fin spacing (fins/ft) 168 168 144 168 168 144
Frontal surface area (m²) 5.7 6.9 6.9 11.3 11.7 13.7
Airflow
Standard unit (m
3
/h) 42500 50400 69300 77200 84700 98500
Low noise unit (m
3
/h) 34500 40900 56300 62700 68800 80000
Condenser fans
Number of fans 4468812
Fan speed
Standard unit (rpm) 690
Low noise unit (rpm) 560
Nominal fan power
Standard unit (kW) 0.85
Low noise unit (kW) 0.54
Current fan amps
Standard unit (A) 2.4
Low noise unit (A) 1.2
Minimum Starting/
Operating Ambient (1) (°C) 7 Standard units/-18 Low ambient units
Refrigerant R134a
Number of Independent
Refrigerant Circuits 111111
Refrigerant Charge (kg) 22 26 36 44 52 72
Operating Weight (2) (kg) 810 890 1090 1535 1770 2050
Shipping Weight (2) (kg) 1020 1100 1300 1870 2170 2450
Hot gas connection (inches) 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
Liquid connection (inches) 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
Unit size 208 209 211 213 215 216
Condenser
Condenser type Aluminium fins/copper tubes
Fin spacing (fins/ft) 168 168 144 168 168 144
Frontal surface area (m²) 5.7 6.9 6.9 11.3 11.7 13.7
Airflow
Standard unit (m
3
/h) 42500 50400 69300 77200 84700 98500
Low noise unit (m
3
/h) 34500 40900 56300 62700 68800 80000
Condenser fans
Number of fans 2 x 2 2 x 2 2 x 3 2 x 4 2 x 4 2 x 6
Fan speed
Standard unit (rpm) 690
Low noise unit (rpm) 560
Nominal fan power
Standard unit (kW) 0.85
Low noise unit (kW) 0.54
Current fan amps
Standard unit 2.4
Low noise unit 1.2
Minimum Starting/
Operating Ambient (1) (°C) 7 Standard units/-18 Low ambient units
Refrigerant R134a
Number of Independent
Refrigerant Circuits 222222
Refrigerant Charge (kg) 2 x 11 2 x 13 2 x 18 2 x 22 2 x 26 2 x 36
Operating Weight (2) (kg) 810 890 1090 1535 1770 2050
Shipping Weight (2) (kg) 1020 1100 1300 1870 2170 2450
Hot gas connection (inches) 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8
Liquid connection (inches) 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8
(1) Based on a 2.2 m/s wind across the condenser
(2) With aluminium fins