EasyManuals Logo
Home>Trane>Furnace>S8B1B080M4PSC

Trane S8B1B080M4PSC User Manual

Trane S8B1B080M4PSC
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #10 background imageLoading...
Page #10 background image
10
S8XB-SVX001-1A-EN
MODEL
S8*1B080M4PSC
(a)
S8*1C080M5PSC
(a)
S8*1C100M5PSC
(a)
S8*1D120M5PSC
(a)
FLA 9.2 10.9 10.9 10.9
COMBUSTION FAN - Type
PSC PSC PSC PSC
Drive - No. Speeds
Direct - 1 Direct - 1 Direct - 1 Direct - 1
Motor RPM 3300 3300 3300 3300
Volts/Ph/Hz 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60
FLA 0.29 0.30 0.33 0.33
Inducer Orifice 1.75 1.80 2.50 2.15
FILTER - Furnished? No No No No
Type Recommended High Velocity High Velocity High Velocity High Velocity
Hi Vel. (No.-Size-Thk.)
1 - 16 X 25 - 1 in. 1 - 20 X 25 - 1 in. 1 - 20 X 25 - 1 in. 1 - 24 X 25 - 1 in.
VENT PIPE DIAMETER - Min. (in.)
4 Round 4 Round 4 Round 4 Round
HEAT EXCHANGER - Type
Aluminized Steel Aluminized Steel Aluminized Steel Aluminized Steel
Gauge (Fired)
20 - 19 20 - 19 20 - 19 20 - 19
ORIFICES - Main
Nat. Gas Qty. - Drill Size
4 - 45 4 - 45 5 - 45 6 - 45
L.P. Gas Qty. - Drill Size
4 - 56 4 - 56 5 - 56 6 - 56
GAS VALVE
Redundant - Single Stage Redundant - Single Stage Redundant - Single Stage Redundant - Single Stage
PILOT SAFETY DEVICE - Type 120 V SiNi Igniter 120 V SiNi Igniter 120 V SiNi Igniter 120 V SiNi Igniter
BURNERS - QTY
4 4 5 6
POWER CONN. - V/Ph/HZ
(e)
120 / 1 / 60 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60
Ampacity (Amps)
12.0 14.1 14.1 14.1
Max. Overcurrent Protection (Amps)
15 15 15 15
PIPE CONN. SIZE (IN.)
1/2 1/2 1/2 1/2
Model
S8X2A040M3PSC
(a)
S8X2B060M4PSC
(a)
S8X2B080M4PSC
(a)
Type Upflow / Horizontal / Downflow Upflow / Horizontal / Downflow Upflow / Horizontal / Downflow
RATINGS
(b)
1st Stage Input BTUH 26,000 39,000 52,000
1st Stage Capacity BTUH (ICS) 20,900 31,500 42,500
2nd Stage Input BTUH 40,000 60,000 80,000
2nd Stage Capacity BTUH (ICS)
(c)
32,200 48,700 65,000
1st Stage Temp. Rise (Min. - Max.) °F
20 - 50 20 - 50 25 - 55
2nd Stage Temp. Rise (Min. - Max.) °F
30 - 60 30 - 60 30 - 60
AFUE (%)
(c)
80 80 80
Return Air Temp. (Min. - Max.) °F
55°F - 80°F 55°F - 80°F 55°F - 80°F
BLOWER DRIVE DIRECT DIRECT DIRECT
Diameter - Width (in.)
11 X 8 11 X 8 11 X 8
No. Used 1 1 1
Speeds (No.)
(d)
CTM - 9 CTM - 9 CTM - 9
CFM vs. in. w.g.
See Fan Performance Table See Fan Performance Table See Fan Performance Table
Motor HP
1/2 3/4 3/4
R.P.M. 1050 1050 1050
Volts / Ph / Hz 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60
FLA 6.4 9.2 9.2
COMBUSTION FAN - Type
PSC PSC PSC
Drive - No. Speeds
Direct - 2 Direct - 2 Direct - 2
Motor RPM
3300/2600 3300/2600 3300/2600
Volts/Ph/Hz 120 / 1 / 60 120 / 1 / 60 120 / 1 / 60
FLA 0.30 0.30 0.33
Inducer Orifice 1.20 1.40 1.75
FILTER - Furnished? No No No
Type Recommended High Velocity High Velocity High Velocity
Hi Vel. (No.-Size-Thk.)
1 - 14 X 25 - 1 in. 1 - 16 X 25 - 1 in. 1 - 16 X 25 - 1 in.
VENT PIPE DIAMETER - Min. (in.)
4 Round 4 Round 4 Round
HEAT EXCHANGER - Type
Aluminized Steel Aluminized Steel Aluminized Steel
Gauge (Fired)
20 - 19 20 - 19 20 - 19
ORIFICES - Main
Nat. Gas Qty. - Drill Size
2 - 45 3 - 45 4 - 45
L.P. Gas Qty. - Drill Size
2 - 56 3 - 56 4 - 56
GAS VALVE
Redundant - Two Stage Redundant - Two Stage Redundant - Two Stage
PILOT SAFETY DEVICE - Type 120 V SiNi Igniter 120 V SiNi Igniter 120 V SiNi Igniter
BURNERS - QTY
2 3 4
PPrroodduucctt SSppeecciiffiiccaattiioonn

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane S8B1B080M4PSC and is the answer not in the manual?

Trane S8B1B080M4PSC Specifications

General IconGeneral
BrandTrane
ModelS8B1B080M4PSC
CategoryFurnace
LanguageEnglish