EasyManuals Logo
Home>Trane>Furnace>TUX2B060A9362A

Trane TUX2B060A9362A User Manual

Trane TUX2B060A9362A
38 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #17 background imageLoading...
Page #17 background image
18-CD19D8-18 17
Installer’s Guide
RAIN CAP
COMBUSTION AIR
STRAP
(FIELD SUPPLIED)
COMBUSTION
AIR
VENT
ELBOW
(FIELD
SUPPLIED)
VENT
1" + 1/2"
3" PIPING
2", 2-1/2"
or 3" PIPING
REDUCING
COUPLING,
FIELD SUPPLIED
IF NEEDED
SEAL ALL
WALL CAVITIES
9" MINIMUM
9" MINIMUM
9" MINIMUM
POSSIBLE CONFIGURATIONS FOR TWO PIPE VENTING SYSTEMS
9" MINIMUM
9" MINIMUM
j
ELBOW AND TEE MUST BE
AS CLOSE TOGETHER
AS POSSIBLE
NOTE: VENT AND INLET MUST BE SUPPORTED
AT A MAXIMUM OF 3' INTERVALS
BAYAIR30AVENTA
TEE
BAYVENT200B
k
40" UPFLOW OR
DOWNFLOW MODELS
SEE VENTING TABLE
OUTSIDE
WALL
NOTE: ANY FITTINGS PASSING
THROUGH AN UNHEATED SPACE
MUST BE INSULATED.
FIRST SUPPORT SHOULD BE AS
CLOSE TO FURNACE CONNECTION
AS POSSIBLE.
UPWARD PITCH -- 1/4" PER FOOT
STRAPS OR OTHER SUITABLE SUPPORTS
AT MAXIMUM OF 3'-0" INTERVALS
COMBUSTION
AIR INLET
USE ONLY
APPROVED
TERMINATION
HORIZONTAL VENTING THROUGH WALL

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Trane TUX2B060A9362A and is the answer not in the manual?

Trane TUX2B060A9362A Specifications

General IconGeneral
BrandTrane
ModelTUX2B060A9362A
CategoryFurnace
LanguageEnglish

Related product manuals