13
PROBLEM
No lights on the AGS
Remote are on
Generator automatically
comes on but does not stay
on.
Generator turns on when
batteries are charged and
air conditioner/heaters are
off.
Generator does not
automatically turn on when
AGS control attempts to
turn on.
Generator does not
automatically turn OFF
after the AGS system runs
the generator for two
hours.
AGS System starts
generator at too high of a
DC voltage.
SOLUTION
Check data cable connected to
AGS Remote Panel and AGS
Control Module. Check for 12 VDC
at AGS Controller (wires #5 and
#13).
Verify that the Generator Hour
Meter Signal (wire #3) is connected
to the AGS Control Module.
Verify Battery Sense Positive (wire
#12) connection.
Check the preheat, if required
(wires #8 and #16) and start signal
connections (wires #1 and #9).
If the battery voltage did not rise
above 13.5 VDC, this is normal
operations. Otherwise check the
stop signal connections (wire #2
and #10).
Verify quality of Power/Sense
negative connection (wire #13).
TROUBLESHOOTING GUIDE
The following is a list of troubleshooting items. Please see
page #8 for the installation diagram. A qualified service technician
should be contacted to service your system. Refer to the installation
diagram for more information.