Johnson Controls Unitary Products 5
824755-YTG-C-0912
PHYSICAL & ELECTRICAL DATA - COOLING ONLY
MODELS
Models
18B 24B 30B 36C 42D 48D 60D
Blower - Diameter x Width
10 x 8 10 x 8 10 x 8 11 x 10 11 x 10 11 x 10 11 x 10
Motor
HP
1/3 HP 1/3 HP 1/3 HP 1/2 HP 1/2 HP 3/4 HP 3/4 HP
Nominal RPM
1050 1050 1050 1050 1050 1050 1050
Voltage
208/230 208/230 208/230 208/230 208/230 208/230 208/230
Full Load Amps @230V
2.3 2.3 2.3 3.2 3.2 4.9 4.9
Filter
1
Type DISPOSABLE OR PERMANENT
Size
16 x 20 x 1 16 x 20 x 1 16 x 20 x 1 20 x 20 x 1 22 x 20 x 1 22 x 20 x 1 22 x 20 x 1
Permanent Type Kit
1PF0601BK 1PF0601BK 1PF0601BK 1PF0602BK 1PF0603BK 1PF0603BK 1PF0603BK
Shipping /
Operating Weight (lbs.)
116/104 121/106 121/106 153/138 169/151 172/154 175/157
1. Field supplied.
KW & MBH CONVERSIONS - FOR TOTAL POWER INPUT REQUIREMENT
For a power distribution voltage that is different than the provided nominal voltage, multiply the kW and MBH data from the table by
the conversion factor in the following table.
DISTRIBUTION POWER NOMINAL VOLTAGE CONVERSION FACTOR
208V 240V 0.75
220V 240V 0.84
230V 240V 0.92
ELECTRICAL DATA - COOLING ONLY
Models
Motor FLA
1
Minimum Circuit Ampacity
MOP
2
Minimum Wire
Size (AWG)
3
208V 230V 208V 230V
18B
24B
30B
2.7 2.3 3.4 2.9 15 14
36C
42D
3.6 3.2 4.5 4.0 15 14
48D
60D
5.3 4.9 6.6 6.1 15 14
1. FLA = Full Load Amps.
2. MOP = Maximum Overcurrent Protection device; must be HACR type circuit breaker or time delay fuse.
3. 75C, copper wire only. If wire other than non-plated, 75C ambient, copper wire is used, consult applicable tables of the NEC and local codes..
ELECTRICAL HEAT: MINIMUM FAN SPEED
1
Heater Kit Models
2,3
Nom. kW
@240V
Air Handler Models
AHV18B AHV24B AHV30B AHV36C AHV42D AHV48D AHV60D
6HK(0,1)6500206 2.4kW Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D)
6HK(0,1)6500506 4.8kW Low (D) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D)
6HK(0,1)6500806 7.7kW Med-Low (C) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D)
6HK(0,1)6501006
6HK06501025
9.6kW Med-Low (C) Low (D) Low (D) Low (D) Low (D) Low (D) Low (D)
6HK(1,2)6501306 12.5kW - Med-Low (C) Med-Low (C) Low (D) Low (D) Low (D) Low (D)
6HK(1,2)6501506
6HK06501525
14.4kW - Med-Low (C) Med-Low (C) Med-Low (C) Low (D) Low (D) Low (D)
6HK(1,2)6501806
6HK06501825
17.3kW - - - Med-Low (C) Med-Low (C) Low (D) Low (D)
6HK(1,2)6502006
6HK16502025
19.2kW - - - Med-High (B) Med-High (B) Low (D) Low (D)
6HK(1,2)6502506
6HK16502525
24kW------Low (D)
1. The referenced letter in this table is for the heat jumper tap.
2. (0,1) - 0 = no circuit breaker OR 1 = with circuit breaker.
3. (1,2) - 1 = with circuit breaker, no breaker jumper bar OR 2 = with circuit breaker & breaker jumper bar.