Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed
temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
HIGH CFM
Continued on next page.
COOLING PERFORMANCE DATA - HIGH CFM 2-STAGE OPERATION
OUTDOOR UNIT MODEL NO. CZH03611(C)
INDOOR COIL MODEL NO. FC62D + MV12D
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1100 1200 1300
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 35.7 38.1 38.5 41.2 45.8 37.2 39.1 38.8 41.7 46.1 38.6 40.1 39.1 42.1 46.3
S.C. 34.5 31.9 27.3 26.9 21.2 36.1 33.4 28.6 27.7 22.1 37.5 35.0 29.9 28.4 22.9
K.W. 1.71 1.74 1.74 1.79 1.82 1.74 1.76 1.76 1.81 1.84 1.78 1.79 1.78 1.84 1.86
75
T.C. 34.6 36.5 36.7 39.5 43.6 35.9 37.4 37.1 40.0 43.9 37.1 38.2 37.5 40.4 44.2
S.C. 33.6 31.1 26.5 26.0 20.6 34.8 32.6 27.6 27.0 21.4 36.0 34.1 28.8 27.9 22.1
K.W. 1.98 2.00 2.00 2.05 2.07 2.00 2.02 2.01 2.06 2.09 2.04 2.05 2.04 2.09 2.12
85
T.C. 33.6 35.0 35.0 37.8 41.5 34.6 35.7 35.4 38.3 41.8 35.5 36.4 35.9 38.7 42.0
S.C. 32.6 30.3 25.6 25.2 20.0 33.6 31.8 26.6 26.3 20.6 34.5 33.3 27.7 27.4 21.2
K.W. 2.24 2.26 2.25 2.30 2.33 2.26 2.28 2.27 2.32 2.35 2.30 2.30 2.30 2.34 2.38
95
T.C. 32.5 33.4 33.2 36.1 39.4 33.3 34.0 33.7 36.6 39.6 34.0 34.5 34.2 37.1 39.8
S.C. 31.6 29.4 24.7 24.3 19.4 32.3 31.0 25.6 25.6 19.9 33.0 32.4 26.6 26.9 20.3
K.W. 2.50 2.52 2.51 2.55 2.59 2.52 2.53 2.53 2.57 2.60 2.56 2.56 2.56 2.59 2.63
105
T.C. 30.7 31.5 31.2 33.7 37.0 31.5 32.0 31.6 34.2 37.2 32.1 32.6 32.0 34.7 37.4
S.C. 29.9 28.4 23.7 23.6 18.6 30.6 29.6 24.7 24.8 19.0 31.3 30.6 25.7 25.9 19.4
K.W. 2.89 2.90 2.90 2.94 2.97 2.92 2.92 2.91 2.96 2.99 2.95 2.95 2.94 2.98 3.02
115
T.C. 29.0 29.6 29.2 31.3 34.7 29.7 30.2 29.5 31.8 34.9 30.4 30.7 29.8 32.3 35.0
S.C. 28.3 27.5 22.8 22.9 17.9 29.0 28.2 23.8 23.9 18.2 29.6 28.9 24.8 24.9 18.5
K.W. 3.28 3.28 3.27 3.32 3.35 3.30 3.29 3.29 3.33 3.37 3.33 3.32 3.31 3.35 3.40
125
T.C. 27.3 27.7 27.2 29.0 32.4 28.0 28.3 27.4 29.5 32.6 28.6 28.8 27.7 30.0 32.7
S.C. 26.7 26.5 21.9 22.2 17.2 27.3 26.8 22.9 23.1 17.4 28.0 27.1 24.0 24.0 17.6
K.W. 3.66 3.65 3.65 3.70 3.73 3.68 3.67 3.66 3.71 3.75 3.71 3.70 3.69 3.73 3.78
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handlers Coils
T.C. S.C. KW
AV*36 – 0.98 0.99 1.04
AV/SV*48 – 0.99 1.00 1.04
AHX36 – 0.98 0.99 1.04
AHX42 – 1.00 1.01 1.04
AHX48 – 0.99 1.01 1.04
AHX60 – 1.01 1.04 1.05
MV12B FC/MC/PC43B 0.98 0.98 1.03
MV12B FC/MC/PC43C 0.98 0.98 1.03
MV16C FC/MC/PC43C 0.99 0.99 1.01
MV12D FC/MC/PC48D 0.98 0.98 1.00
MV12D UC48D 0.98 0.98 1.00
MV16C FC/MC/PC48C 0.99 0.99 1.00
MV16C FC/MC/PC48D 0.99 0.99 1.00
MV16C UC48D 0.99 0.99 1.00
MV20D FC/MC/PC48D 1.00 1.00 1.00
MV20D UC48D 1.00 1.00 1.00
MV12D FC/MC62D 1.00 1.00 1.00
MV20D FC/MC62D 1.01 1.01 1.00