EasyManuals Logo
Home>York>Air Conditioner>DJ 036

York DJ 036 User Manual

York DJ 036
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #21 background imageLoading...
Page #21 background image
036-21687-002-A-1105
Unitary Products Group 21
TABLE 16: DJ036 COOLING CAPACITIES (3 TON)
Air on Evap-
orator Coil
Temperature of Air on Condenser Coil
75°F 85°F
CFM
WB
(°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
Total
Cap.
1
(MBH)
Total
2
Input
(kW)
Sensible Capacity (MBH)
1
Return Dry Bulb (°F)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
900
72 44 2.3 24 21 19 16 14 - - 41 2.5 23 20 18 15 12 - -
67 42 2.3 30 28 25 23 20 18 15 38 2.5 29 26 24 21 18 16 13
62 40 2.3 40 35 33 30 28 25 23 35 2.5 35 32 30 27 25 22 20
57 39 2.3 39 37 35 32 30 27 25 35 2.5 35 34 31 28 26 23 21
1050
72 44 2.2 26 23 20 17 14 - - 42 2.5 25 22 19 16 13 - -
67 42 2.3 33 30 27 24 21 18 15 39 2.5 31 28 25 22 19 16 13
62 40 2.3 40 38 35 32 29 26 23 35 2.5 35 34 32 29 26 23 20
57 39 2.3 39 38 37 34 31 28 25 35 2.5 35 35 33 30 27 24 21
1200
72 44 2.2 28 25 21 18 14 - - 43 2.5 27 24 20 17 13 - -
67 43 2.3 35 32 28 25 21 18 14 40 2.5 34 31 27 24 20 17 13
62 40 2.3 40 40 37 33 30 26 23 36 2.5 36 36 34 31 27 24 20
57 39 2.3 39 39 39 36 32 29 25 36 2.5 36 36 36 32 29 25 22
1350
72 45 2.2 30 26 22 18 14 - - 43 2.5 29 25 21 17 13 - -
67 43 2.3 37 33 29 25 21 18 14 40 2.5 36 32 28 24 20 16 12
62 41 2.3 41 41 39 35 31 27 23 37 2.5 37 37 36 32 28 24 20
57 40 2.3 40 40 40 36 32 28 24 36 2.5 36 36 36 32 28 24 20
1500
72 46 2.3 32 27 23 18 14 - - 44 2.5 31 27 22 18 13 - -
67 44 2.3 40 35 31 26 22 17 13 41 2.5 39 34 30 25 21 16 12
62 42 2.3 42 42 42 37 33 28 24 37 2.5 37 37 37 33 28 24 19
57 41 2.3 41 41 41 36 32 27 23 37 2.5 37 37 37 32 28 23 19
95°F 105°F
900
72 38 2.7 21 19 16 14 11 - - 35 3.0 20 17 15 12 10 - -
67 35 2.7 27 24 22 19 17 14 12 31 2.9 25 23 20 18 15 12 10
62 30 2.7 30 29 27 24 22 19 17 27 3.0 27 26 24 21 19 16 14
57 30 2.7 30 30 27 25 22 19 17 27 3.0 27 27 25 22 20 17 15
1050
72 39 2.7 24 21 18 15 12 - - 36 3.0 22 19 16 13 10 - -
67 36 2.7 30 27 24 21 18 15 12 32 2.9 28 25 22 19 16 13 10
62 31 2.7 31 31 30 26 23 20 17 28 2.9 28 28 26 23 20 17 14
57 31 2.7 31 31 30 27 24 21 18 28 2.9 28 28 27 24 21 18 15
1200
72 41 2.7 26 23 19 16 12 - - 37 2.9 25 21 18 14 11 - -
67 37 2.7 33 30 26 23 19 16 12 33 2.8 31 28 24 21 17 14 10
62 32 2.7 32 32 32 29 25 22 18 29 2.9 29 29 29 25 22 18 15
57 32 2.7 32 32 32 29 25 22 18 29 2.9 29 29 30 26 23 19 16
1350
72 41 2.7 28 24 20 16 12 - - 37 3.0 27 23 19 15 11 - -
67 37 2.7 35 31 27 23 19 15 11 33 2.9 32 29 25 21 17 13 9
62 32 2.7 32 32 32 28 24 20 16 29 2.9 29 29 29 25 21 17 13
57 33 2.7 33 33 33 29 25 21 17 29 2.9 29 29 30 26 22 18 14
1500
72 42 2.7 30 26 21 17 12 - - 37 3.1 28 24 20 15 11 - -
67 38 2.7 38 33 29 24 20 15 11 33 2.9 33 31 27 22 18 13 9
62 33 2.7 33 33 33 28 24 19 15 29 3.0 29 29 29 24 20 15 11
57 33 2.7 33 33 33 29 24 20 15 29 3.0 29 29 29 25 20 16 11
115°F 125°F
900
72 32 3.3 18 16 13 11 8 - - 28 3.7 17 14 12 9 7 - -
67 27 3.1 232118161311 8 24 3.3 2219171411 9 6
62 24 3.2 24 23 21 18 16 13 11 21 3.5 21 20 18 15 13 10 8
57 25 3.2 25 25 23 20 17 15 12 22 3.5 22 22 20 18 15 13 10
1050
72 32 3.3 21 18 15 12 9 - - 29 3.5 19 16 13 10 7 - -
67 28 3.0 262320171411 8 24 3.2 2422181512 9 6
62 25 3.1 25 24 23 20 17 14 11 21 3.4 21 21 20 17 14 11 8
57 25 3.1 25 25 25 22 19 16 13 22 3.4 22 22 22 19 16 13 10
1200
72 33 3.2 23 20 16 13 9 - - 29 3.4 21 18 14 11 7 - -
67 29 3.0 292622191512 8 25 3.1 252420171310 6
62 25 3.1 25 25 25 22 18 15 11 22 3.3 22 22 22 18 15 11 8
57 26 3.1 26 26 27 24 20 17 13 22 3.3 22 22 22 21 18 14 11
1350
72 33 3.3 25 21 17 13 9 - - 29 3.6 23 19 15 11 7 - -
67 29 3.1 292723191511 8 24 3.2 242421171310 6
62 25 3.2 252525211713 9 21 3.4 2121211713 9 5
57 26 3.2 26 26 26 22 18 14 10 22 3.4 22 22 22 19 15 11 7
1500
72 33 3.4 27 22 18 13 9 - - 28 3.8 25 20 16 11 7 - -
67 28 3.2 282825201611 7 24 3.4 2424231814 9 5
62 25 3.3 252525201611 7 21 3.6 2121211612 7 3
57 25 3.3 252525211612 8 22 3.6 2222221713 8 4
1. The capacities are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.