EasyManuals Logo

York Eco 2 User Manual

York Eco 2
36 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #20 background imageLoading...
Page #20 background image
JOHNSON CONTROLS
20
FORM 100.50-SU3 (1207)
Programming
“COMFORT VENTILATION FOR COOLING
ENABLED” – must be turned ON under the COOLING
SETUP tab in the Simplicity PC software.
“COMFORT VENTILATION FOR HEATING
ENABLED” – must be turned ON under the HEATING
SETUP tab in the Simplicity PC software.
“COMFORT VENTILATION UPPER SETPOINT”
– must be programmed under the COOLING SETUP
or HEATING SETUP tab in the Simplicity PC software.
The default value is 80.0º F.
“COMFORT VENTILATION LOWER SETPOINT”
– must be programmed under the COOLING SETUP
or HEATING SETUP tab in the Simplicity PC software.
The default value is 70.0º F.
EXCESSIVE SUPPLY AIR TEMPERATURE CONTROL
(COOLING)
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“SUPPLY AIR TEMP LIMIT FOR COOLING
ENABLED” – must be turned ON using Parameter 14
under the PROGRAM key on the Simplicity control
board or under the COOLING SETUP tab in the
Simplicity PC software.
“SUPPLY AIR TEMP LIMIT COOLING SETPOINT”
– must be programmed using Parameter 15 under the
PROGRAM key on the Simplicity control board or
under the COOLING SETUP tab in the Simplicity PC
software. The range is 40.0º F – 65.0º F with a default
valve of 50.0º F.
EXCESSIVE SUPPLY AIR TEMPERATURE CONTROL
(HEATING)
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.
Programming
“SUPPLY AIR TEMP LIMIT FOR HEATING
ENABLED” – must be turned ON using Parameter 16
under the PROGRAM key on the Simplicity control
board or under the HEATING SETUP tab in the
Simplicity PC software.
“SUPPLY AIR TEMP LIMIT HEATING SETPOINT”
– must be programmed using Parameter 17 under the
PROGRAM key on the Simplicity control board or
under the HEATING SETUP tab in the Simplicity PC
software. The range is 100.0º F – 180.0º F with a default
valve of 135.0º F.
VENTILATION – LOW AMBIENT MINIMUM POSITION
RESET
Field Wiring
No additional connections required.
Misc. Connections
No additional connections required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York Eco 2 and is the answer not in the manual?

York Eco 2 Specifications

General IconGeneral
BrandYork
ModelEco 2
CategoryAir Conditioner
LanguageEnglish

Related product manuals