036-21121-002 Rev. B (0103)
Unitary Products Group 15
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree belowthe listed temperature.
1 Phase
3 Phase
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. H1RA042S06, H1RA042S(25,46)
INDOOR COIL MODEL NO. G1FA048S21
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 1200 1400 1600
ID DB (°F) 85 80 70 85 80 70 85 80 70
ID WB (°F) 72 67 57 72 67 57 72 67 57
75
T.C. 47.2 44.1 41.2 47.5 44.6 41.9 47.9 45.1 42.6
S.C. 30.2 29.6 29.4 31.9 31.1 31.0 33.6 32.6 32.6
K.W 3.90 3.85 3.78 4.05 3.99 3.94 4.19 4.14 4.09
85
T.C. 45.5 42.1 38.5 45.9 42.8 39.3 46.3 43.4 40.2
S.C. 29.8 28.9 28.1 31.4 30.7 30.0 33.0 32.5 31.9
K.W 4.13 4.06 3.96 4.28 4.21 4.13 4.43 4.36 4.29
95
T.C. 43.9 40.2 35.7 44.3 41.0 36.8 44.8 41.8 37.8
S.C. 29.5 28.2 26.9 30.9 30.3 29.1 32.4 32.4 31.2
K.W 4.36 4.27 4.14 4.52 4.43 4.31 4.67 4.59 4.49
105
T.C. 40.5 36.3 32.0 41.2 37.1 32.8 42.0 38.0 33.7
S.C. 28.1 26.7 25.1 29.9 28.8 27.2 31.7 30.9 29.3
K.W 4.58 4.44 4.30 4.74 4.60 4.47 4.89 4.77 4.64
115
T.C. 37.1 32.3 28.3 38.2 33.3 28.9 39.2 34.2 29.6
S.C. 26.8 25.1 23.3 29.0 27.2 25.4 31.1 29.4 27.4
K.W 4.81 4.62 4.45 4.96 4.78 4.62 5.10 4.95 4.79
125
T.C. 33.7 28.4 24.5 35.1 29.4 25.0 36.4 30.4 25.4
S.C. 25.5 23.5 21.5 28.0 25.7 23.5 30.5 27.9 25.5
K.W 5.04 4.79 4.61 5.18 4.96 4.78 5.32 5.13 4.94
NOTE: ALL CAPACITIES ARE NET WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
N1AHC1606 G2FD042(S,H)21 0.96 0.96 0.99
N1AHC1606 G2FD048(S,H)21 1.00 1.00 1.01
F2RP/F2FP042 0.96 0.95 0.99
F2FP048 0.99 0.99 0.99
G1FA048S17 0.98 1.00 1.00
G1FA060S21,24 1.02 1.02 1.00
G1HD048 0.99 0.99 1.01
G1NA036S21C 0.98 0.93 0.99
G1NA048S21D 0.99 0.94 1.00
G1UA048S17 0.98 1.00 1.00
G1UA048S21 1.00 1.00 1.00
G1UA060S21,24 1.02 1.03 1.00
G2FD042(S,H)21 0.96 0.96 0.99
G2FD046(S,H)17 0.98 0.98 1.00
G2FD048(S,H)21,24 1.00 1.00 1.01
G2FD060(S,H)24 1.02 1.02 1.00
Air Handler Coil
T.C. S.C. KW
N1AHC1646 G2FD042(S,H)21 0.98 0.99 1.00
N1AHC1646 G2FD048(S,H)21 0.99 1.01 1.01
F2RP/F2FP042 0.95 0.95 0.99
F2FP048 0.99 0.99 0.99
G1FA060S21,24 1.02 1.02 1.00
G1NA036S21C 0.98 0.93 0.99
G1NA048S21D 0.99 0.94 1.00
G1UA048S21 1.00 1.00 1.00
G1UA060S21,24 1.02 1.03 1.00
G2FD042(S,H)21 0.96 0.96 0.99
G2FD046(S,H)17 0.98 0.98 1.00
G2FD048(S,H)21,24 1.00 1.00 1.01