550.13-TG2Y (799)
12 Unitary Products Group
TABLE 14: PHYSICAL DATA
DESCRIPTION
MODEL
LEU360 LEU480 LEU600
EVAPORATOR
COIL
Rows Deep X Rows High 4 x 32 4 x 40 4 x 50
Finned Length, inches 93 96 96
Face Area, feet
2
26.0 33.4 41.7
Tube (copper) OD, inches 1/2 1/2 1/2
Fins (Aluminum) per 1 inch 12 12 12
CENTRIFUGAL
BLOWERS (2 PER UNIT)
Diameter X Width, inches (Forward Curved) 18 x 18 18 x 18 20 x 18
FILTERS (THROWAWAY)
Size and Quantity Per
Model, inches
16 x 25 x 1 - - 6
20 x 20 x 1 - 12 -
20 x 22-1/4 x 1 - 3 -
20 x 25 x 1 10 - 3
25 x 25 x 1 - - 6
Total Face Area / feet
2
34.7 42.6 53.1
OPERATING CHARGE
LBS
(R
EFRIGERANT
- 22)
System 1 18 12 14
System 2 - 12 19
DRAINABLE HOT WATER
COIL ACCESSORY
Tube (copper) OD, inches 1/2 1/2 1/2
Rows Deep 2 2 2
Fins (Aluminum) per 1 inch 12 12 8
Face Area, feet
2
21.2 27.2 27.2
Connections (Supply & Return), inches 13/8 OD (copper) 1-5/8 OD (copper)
NON-FREEZE, STEAM
DISTRIBUTING COIL
ACCESSORY
Tube (copper) OD, inches 1 (Outside) 5/8 (in.)
N/A
Rows Deep 1
Fins (Aluminum) per 1 inch 8
Face Area, feet
2
18.2
Connection, (Brass)
Inches (NPTE)
Inlet 2
Outlet 1-1/2
COMPONENT WEIGHT
Basic Unit (Less Motor & Drive) 690 1170 1500
Shipping Weight (lbs) 990 1170
Operating Weight (lbs) 1115 1310
Accessories
Hot Water Coil 150 190 190
Steam Coil 160 - -
Supply Air Plenum 125 - -
Return Air Grille 25 - -
Blower Motor (1750 RPM)
120 (5HP) - -
150 (7.5HP) 150 (7.5HP) 150 (7.5HP)
180 (10HP) 180 (10HP) 180 (10HP)