505428-YTG-V-0417
Johnson Controls Unitary Products 13
NC300 Indoor Unit Physical Data
Component
Models
NC300
1
2
1
Motors, Drive and Overload Kits must be ordered
separately for the NC300. The Motor Drive and
Overload Kits are to be field installed.
2
IntelliSpeed discrete fan control option for NC300 is
field installed only. Please refer to price pages or UST
to select proper motor, drive, and IntelliSpeed VFD
kit.
Nominal Tonnage 25
DIMENSIONS (inches)
Length
100.1
Width
38.1
Height
74.6
WEIGHTS (lb)
Unit Shipping
1067
Unit Operating With
5 hp Motor & Drive
1130
7.5 hp Motor & Drive
1157
5 hp Motor & Drive With Field Installed VFD Intellispeed 1158
7.5 hp Motor & Drive Field Installed VFD Intellispeed 1187
INDOOR BLOWER (Forward Curve)
Diameter x Width 18 X 18
Quantity 2
INDOOR COIL
Face area (Sq. Ft.) 25.8
Rows 4
Fins per inch 16
Tube diameter 3/8
Circuitry Type Split
Refrigerant Control TEV
SYSTEM DATA
No. Refrigeration Circuits 1
Suction Line OD (in.) 2 1/8
Liquid Line OD (in.) 7/8
FILTERS
Size and Quantity Per
Model (In.)
20 x 25 x 2 10
FACE AREA (SQ. FT.) 34.7
ACCESSORY
HOT WATER COIL DATA
Face area (Sq. Ft.) 21.2
Rows 2
Fins per inch 12
Tube diameter (Copper) OD (In.) 1/2
Connections (Supply and Return) OD (In.) 1 3/8
Weight (lb) 150
SYSTEM COIL DATA
Face area (Sq. Ft.) 18.2
Rows 1
Fins per inch 8
Tube diameter (Copper) (In.) 1
Connection, (NPTE) (In.)
Inlet 2
Outlet 1-1/2
Weight (lb) 160