EasyManuals Logo
Home>York>Air Handlers>NL090-300

York NL090-300 User Manual

York NL090-300
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #50 background image
505428-YTG-V-0417
50 Johnson Controls Unitary Products
PD240 / ND240 / NM240
Air Over Evaporator Coil
Capacity
1
&
kW
1
These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh. Example: Refer to the appropriate
Blower Performance Table for the BHP of the supply air blower motor, MBh = 3.415 x kW and kW = BHP x 0.746 nameplate rated
motor efficiency.
Outdoor Temperature (°F @ 72% RH)
CFM DB (°F) -10 0 10 20 30 40 50 60
6000
55
MBH 64.6 79.5 97.4 118.8 144.3 174.9 211.4 255.1
KW 15.7 16.5 17.3 18.1 19.0 19.8 20.6 21.4
70
MBH 69.5 84.4 102.3 123.7 149.2 179.8 216.3 260.0
KW 15.4 16.2 17.0 17.9 18.7 19.5 20.3 21.2
80
MBH 63.3 78.3 96.2 117.5 143.1 173.6 210.2 253.8
KW 17.2 18.0 18.8 19.6 20.5 21.3 22.1 23.0
8000
55
MBH 71.6 86.6 104.5 125.8 151.4 181.9 218.5 262.1
KW 15.1 15.9 16.8 17.6 18.4 19.2 20.1 20.9
70
MBH 76.5 91.5 109.4 130.7 156.3 186.8 223.4 267.0
KW 14.8 15.6 16.5 17.3 18.1 19.0 19.8 20.6
80
MBH 70.4 85.3 103.2 124.6 150.1 180.7 217.2 260.9
KW 16.6 17.4 18.3 19.1 19.9 20.7 21.6 22.4
10000
55
MBH 73.3 88.3 106.1 127.5 153.1 183.6 220.1 263.8
KW 15.3 16.1 17.0 17.8 18.6 19.4 20.3 21.1
70
MBH 78.2 93.2 111.0 132.4 158.0 188.5 225.0 268.7
KW 15.0 15.8 16.7 17.5 18.3 19.1 20.0 20.8
80
MBH 72.1 87.0 104.9 126.3 151.8 182.4 218.9 262.6
KW 16.8 17.6 18.5 19.3 20.1 20.9 21.8 22.6

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the York NL090-300 and is the answer not in the manual?

York NL090-300 Specifications

General IconGeneral
BrandYork
ModelNL090-300
CategoryAir Handlers
LanguageEnglish

Related product manuals