EasyManuals Logo

York NM120-240 User Manual

York NM120-240
128 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #14 background imageLoading...
Page #14 background image
505428-YTG-V-0417
14 Johnson Controls Unitary Products
Unit Limitations
1. Rated in accordance with AHRI Standard 110, Range “A” Utilization Voltage.
†. Low Ambient accessories are available to permit stable system operation at ambient temperatures down to 0°F.
Condenser Unit limitations
Size
(Tons)
Model
Unit Voltage
Applied Voltage
1
Outdoor DB Temp
Cooling (°F)
Indoor DB Temp
Cooling (°F)
Outdoor DB Temp
Heating (°F)
Indoor DB Temp
Heating (°F)
Min Max Max Min
Max Min Max Min Max Min
090
(7.5)
PC
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
090
(7.5)
YC
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
120
(10)
PC
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
120
(10)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
150
(12.5)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
180
(15)
PC/PD
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
180
(15)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
240
(20)
PD
208/230-3-60 187 252
125 40 86 68 70 0 80 50
460-3-60 432 504
240
(20)
YC/YD
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630
300
(25)
YC
208/230-3-60 187 252
125 40 86 68 - - - -460-3-60 432 504
575-3-60 540 630