035-17311-000 REV A (1200))
Unitary Products Group 17
TABLE 12: PREDATOR 380V -3-60 HZ
Model Compressors
OD Fan
Motors
Motor, Supply Blower
Pwr Exh
Motor
FLA
Electric Heater
Model No.
Rated
kW
Actual
kW
Heater
Amps
Minimum Circuit
Ampacity
MCA W/ Power Exhaust Max Fuse Size *
Max Fuse Size w/
Pwr. Exh. *
Amps
Amps Amps Amps
Ton-
nage
Voltage
RLA
each
LRA
each
FLA
each
1.5
HP
2
HP
3
HP
5 HP
1.5
HP
2 HP 3 HP 5 HP
1.5
HP
2 HP 3 HP 5 HP
1.5
HP
2
HP
3
HP
5
HP
1.5
HP
2
HP
3
HP
5
HP
7 1/2 380 7.1 64 0.8 3.1 4.1 2.2
None - - - 20.7
21.7 22.9 23.9 25 25 25 30
2TP04510946 9.0 5.6 8.5 20.7
21.7 22.9 23.9 25 25 25 30
2TP04511846 18.0 11.3 17.2 25.3
26.6 28.1 29.3 30 30 30 30
2TP04512446 24.0 15.0 22.8 32.4
33.6 35.1 36.4 35 35 40 40
2TP04513646 34.0 21.3 32.4 44.3
45.6 47.1 48.3 45 50 50 50
10 380 9.0 75 1.6 4.1 5.3 2.2
None - - -
27.6 28.8 29.8 31.0 35 35 35 35
2TP04511846 18.0 11.3 17.2
27.6 28.8 29.8 31.0 35 35 35 35
2TP04512446 24.0 15.0 22.8
33.6 35.1 36.4 37.9 35 40 40 40
2TP04513646 34.0 21.3 32.4
45.6 47.1 48.3 49.8 50 50 50 50
2TP04515446 54.0 33.8 51.4
69.3 70.8 72.1 73.6 70 80 80 80
12 1/2 380 9.6 79 1.6 5.3 8.6 2.2
None - - -
30.1 33.4 32.3 35.6 35 40 40 45
2TP04511846 18.0 11.3 17.2
30.1 33.4 32.3 35.6 35 40 40 45
2TP04512446 24.0 15.0 22.8
35.1 39.2 37.9 42.0 40 40 40 45
2TP04513646 34.0 21.3 32.4
47.1 51.2 49.8 54.0 50 60 50 60
2TP04515446 54.0 33.8 51.4
70.8 74.9 73.6 77.7 80 80 80 80
* Maximum HACR breaker of the same amp size is acceptable.