21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
5.12 4.90 4.72 4.45 4.27 4.14 4.01
Sensitive capacity kW
4.10 3.92 3.78 3.56 3.42 3.31 3.21
21ºC D
15ºC W
Input kW.
1.20 1.37 1.54 1.71 1.88 2.05 2.22
Total capacity kW
5.61 5.36 5.17 4.88 4.68 4.53 4.39
Sensitive capacity kW
4.49 4.29 4.13 3.90 3.74 3.63 3.51
24ºC D
17ºC W
Input kW.
1.26 1.44 1.62 1.81 1.99 2.17 2.35
Total capacity kW
6.10 5.83 5.62 5.30 5.09 4.93 4.77
Sensitive capacity kW
4.88 4.66 4.49 4.24 4.07 3.94 3.82
27ºC D
19ºC W
Input kW.
1.33 1.52 1.71 1.90 2.09 2.28 2.47
Total capacity kW
7.01 6.70 6.46 6.10 5.85 5.67 5.49
Sensitive capacity kW
5.61 5.36 5.17 4.88 4.68 4.53 4.39
32ºC D
23ºC W
Input kW.
1.53 1.75 1.97 2.19 2.40 2.62 2.84
Model: YKHC 12-18
HEATING OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
7.20 5.76 4.80 4.32 4.08 3.60 3.36 3.12
15ºC
Input kW.
2.28 1.82 1.52 1.44 1.37 1.29 1.22 1.06
Capacity kW
8.10 6.48 5.40 4.86 4.59 4.05 3.78 3.51
18ºC
Input kW.
2.57 2.05 1.71 1.62 1.54 1.45 1.37 1.20
Capacity kW
9.00 7.20 6.00 5.40 5.10 4.50 4.20 3.90
20ºC
Input kW.
2.85 2.28 1.90 1.81 1.71 1.62 1.52 1.33
Capacity kW
9.90 7.92 6.60 5.94 5.61 4.95 4.62 4.29
22ºC
Input kW.
3.14 2.51 2.09 1.99 1.88 1.78 1.67 1.46
Capacity kW
11.70 9.36 7.80 7.02 6.63 5.85 5.46 5.07
27ºC
Input kW.
3.71 2.96 2.47 2.35 2.22 2.10 1.98 1.73