21ºC 25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW
13.52 12.94 12.47 11.76 11.29 10.94 10.58
Sensitive capacity kW
10.82 10.35 9.97 9.41 9.03 8.75 8.47
21ºC D
15ºC W
Input kW.
2.96 3.38 3.81 4.23 4.65 5.08 5.50
Total capacity kW
14.81 14.17 13.65 12.88 12.36 11.98 11.59
Sensitive capacity kW
11.85 11.33 10.92 10.30 9.89 9.58 9.27
24ºC D
17ºC W
Input kW.
3.13 3.57 4.02 4.47 4.91 5.36 5.80
Total capacity kW
16.10 15.40 14.84 14.00 13.44 13.02 12.60
Sensitive capacity kW
12.88 12.32 11.87 11.20 10.75 10.42 10.08
27ºC D
19ºC W
Input kW.
3.29 3.76 4.23 4.70 5.17 5.64 6.11
Total capacity kW
18.52 17.71 17.07 16.10 15.46 14.97 14.49
Sensitive capacity kW
14.81 14.17 13.65 12.88 12.36 11.98 11.59
32ºC D
23ºC W
Input kW.
3.78 4.32 4.86 5.41 5.95 6.49 7.03
Model: YKHC-48
HEATING OUTDOOR CONDITIONS
Indoor
Conditions
24ºC D
-6ºC W
-7ºC D
-8ºC W
-15ºC D
-16ºC W
Capacity kW
18.24 14.59 12.16 10.94 10.34 9.12 8.51 7.90
15ºC
Input kW.
5.88 4.70 3.92 3.72 3.53 3.33 3.14 2.74
Capacity kW
20.52 16.42 13.68 12.31 11.63 10.26 9.58 8.89
18ºC
Input kW.
6.62 5.29 4.41 4.19 3.97 3.75 3.53 3.09
Capacity kW
22.80 18.24 15.20 13.68 12.92 11.40 10.64 9.88
20ºC
Input kW.
7.35 5.88 4.90 4.66 4.41 4.17 3.92 3.43
Capacity kW
25.08 20.06 16.72 15.05 14.21 12.54 11.70 10.87
22ºC
Input kW.
8.09 6.47 5.39 5.12 4.85 4.58 4.31 3.77
Capacity kW
29.64 23.71 19.76 17.78 16.80 14.82 13.83 12.84
27ºC
Input kW.
9.56 7.64 6.37 6.05 5.73 5.41 5.10 4.46