Dimension (W*H*D) mm
1350×300×800 1350×300×800 1350×320×800
Packing (W*H*D) mm
1555×370×940 1555×370×940 1555×440×940
Indoor unit
Net/Gross weight kg
48/57 50/59 70/80
Model
YDK250-6D-WL YDK65-6WL; YDK65-6F YDK65-6WL; YDK65-6F
Brand
WEILING WELLING WELLING
Input W
307 138+156 138+156
Capacitor uF
10 3.5×2 3.5×2
Outdoor fan
motor
Speed r/min
740 800 800
Number of rows
2 2 2
Tube pitch(a)x row pitch(b) mm
25.4×22 25.4×22 25.4×22
Fin spacing mm
1.7 1.8 1.8
Fin type (code)
unhydrophilic hydrophilic hydrophilic
Tube outside dia.and type mm
Ф9.53, Ф9.53, Ф9.53,
Coil length x height x width mm
955×915×44 715×1220×44 715×1220×44
Outdoor coil
Number of circuits
8 4 4
Outdoor air flow
m
3
/h
5000 5000 5000
Outdoor noise level dB(A)
57 58 58
Dimension (W*H*D) mm
990×960×360 940×1245×360 940×1245×360
Packing (W*H*D) mm
1120×1090×435 1020×1370×435 1020×1370×435
Outdoor unit
Net/ Gross weight kg
101/106 110/125 110/125
Refrigerant type/Quantity g
R410A/3100 R410A/4000 R410A/4200
Design pressure (high side/low side) MPa
4.2/2.5 4.2/2.5 4.2/2.5
Liquid side mm(inch)
12.7 (1/2) 12.7 (1/2) 12.7 (1/2)
Gas side mm(inch)
19 (3/4) 19 (3/4) 19 (3/4)
Max. pipe length m
30 30 30
Refrigerant
piping
Max. difference in level m
20 20 20
Operation temp
ºC
17~30 17~30 17~30
Ambient temp
ºC
-7~45 -7~45 -7~45
Application area m
2
60~85 80~105 95~120
Qty’per 20’ /40’ /40'HQ set
24/52/62 23/47/50 21/44/50
Notes: 1. Nominal cooling capacities are based on the following conditions:
Indoor temp: 27°CDB, 19°CWB; Outdoor temp: 35°CDB;
2. Nominal heating capacities are based on the following conditions:
Indoor temp: 20°CDB; Outdoor temp: 7°CDB, 6°CWB;
3. Actual noise level may differ, depending on the room structure, etc, since these noise values are from an
anechoic room.