ACH550-01 User's Manual
104 Application macros and wiring
5. Condenser
This application macro is for condenser and liquid cooler
applications where the fan speed is controlled according to the
signals received from the transducer. See the figure below.
When using a direct speed reference in the AUTO mode, the
speed reference must be connected to analogue input 1 (AI1)
and the START command is given with digital input 1 (DI1). In
the HAND/OFF mode, the speed reference and START
command are given through the control panel (operator keypad).
If process PI(D) is used, the feedback signal must be connected
to analogue input 2 (AI2). By default, the setpoint is set from the
control panel, but it can also be changed to analogue input 1.
Process PI(D) must be commissioned and adjusted with
parameters (Group 40: PROCESS PID SET 1) or using the PID
control assistant (recommended).