Technical data 411
ACH550-01 User's Manual
Motor cable length
The tables below show the maximum motor cable lengths for
400 V drives with different switching frequencies. Examples for
using the table are also given.
Under heading “Operational limits”, the “Basic unit” columns
define the cable lengths with which the basic drive unit works
without problems within the drive specification, without installing
Maximum cable lengths (m) for 400 V
Frame
size
EMC limits Operational limits
IEC/EN 61800-3
Second environment
(category C3
1
)
IEC/EN 61800-3
First environment
(category C2
1
) Basic unit
With
du/dt
filters
1kHz 4kHz 8kHz 1kHz 4kHz 8kHz1/4kHz
8/12
kHz
R1 300 300 300 300 300 300 100 100 150
R2 300 300 300 300 100 30 200 100 250
R3 300 300 300 300 75 75 200 100 250
R4 300 300 300 300 75 75 200 100 300
R5 100 100 100 100 100 100 300 150
2
300
R6 100 100
3
100 100
3
300 150
2
300
00577999.xls A
1
See the new terms in section IEC/EN 61800-3:2004 Definitions on page 444.
2
12 kHz switching frequency is not available.
3
Not tested.
Sine filters further extend the cable lengths.
Maximum cable lengths (ft) for 400 V
Frame
size
EMC limits Operational limits
IEC/EN 61800-3
Second environment
(category C3
1
)
IEC/EN 61800-3
First environment
(category C2
1
) Basic unit
With
du/dt
filters
1kHz 4kHz 8kHz 1kHz 4kHz 8kHz1/4kHz
8/12
kHz
R1 980 980 980 980 980 980 330 330 490
R2 980 980 980 980 330 98 660 330 820
R3 980 980 980 980 245 245 660 330 820
R4 980 980 980 980 245 245 660 330 980
R5 330 330 330 330 330 330 980 490
2
980
R6 330 330
3
330 330
3
980 490
2
980
00577999.xls A
1
See the new terms in section IEC/EN 61800-3:2004 Definitions on page 444.
2
12 kHz switching frequency is not available.
3
Not tested.
Sine filters further extend the cable lengths.