EasyManuals Logo
Home>ABB>Control Unit>ACQ580-34

ABB ACQ580-34 Quick Installation Guide

ABB ACQ580-34
22 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #7 background imageLoading...
Page #7 background image
EN – Quick installation guide 7
EN
DA
DE
ES
FI
FR
IT
PL
PT
RU
SV
TR
ZH
Default I/O connections
The default I/O connections of the Water default configuration are shown below.
Wire sizes: 0.14…2.5 mm
2
(26...16 AWG): All terminals.
Tightening torques: 0.5…0.6 N·m (0.4 lbf·ft).
500 ohm
Max.
X1
1…10 kohm
1 SCR
Reference voltage and analog inputs and outputs
2 AI1
Signal cable shield (screen)
3 AGND
Output frequency/speed reference : 0…10 V
4 +10V
Analog input circuit common
5 AI2
Reference voltage 10 V DC
6
Actual feedback: 0…10 V
AGND
7 AO1
8 AO2
Analog input circuit common
Output frequency: 0…10 V
9 AGND
Output current: 0…20 mA
Analog output circuit common
10 +24V
X2 & X3 Aux. voltage output and programmable digital inputs
11 DGND
Aux. voltage output +24 V DC, max. 250 mA
12 DCOM
Aux. voltage output common
13 DI1
Digital input common for all
14 DI2
Stop (0) / Start (1)
15 DI3
Not configured
16 DI4
Constant frequency/speed selection
17 DI5
Not configured
18 DI6
Not configured
Not configured
19 RO1C
X6, X7, X8 Relay outputs
20 RO1A
21 RO1B
Ready run
250 V AC / 30 V DC
2 A
22 RO2C
23 RO2A
24 RO2B
Running
250 V AC / 30 V DC
2 A
25 RO3C
26 RO3A
27 RO3B
X5
Fault (-1)
250 V AC / 30 V DC
2 A
29 B+
Embedded fieldbus
30 A-
31 DGND
S4 TERM
Embedded fieldbus, EFB (EIA-485)
S5 BIAS
Termination switch
X4
Bias resistors switch
34
Safe torque off
OUT1
35 OUT2
36 SGND
37 IN1
38 IN2
X10
40
24 V AC/DC
41
Safe torque off. Factory connection. Both
circuits must be closed for the drive to start. See
chapter 7KH6DIHWRUTXHRIIIXQFWLRQ in the
$&4KDUGZDUHPDQXDO
(3AXD50000[English]).
24 V AC/DC+ in
Ext. 24V AC/DC input to power up the control unit
24 V AC/DC- in
when the main supply is
disconnected.
Total load capacity of the Auxiliary voltage output +24V (X2:10) is 6.0 W (250 mA / 24 V DC).