Drive type
ACQ580-34-
Air flow Losses Type DIN 43653
m
3
/h W
U
N
= 400 V
246A-4 2100 5280 170M5408
293A-4 2100 6400 170M5410
363A-4 2100 8000 170M6410
442A-4 2100 10000 170M6411
505A-4 2100 10000 170M6412
585A-4 2100 12600 170M6414
650A-7 2100 14200 170M6414
U
N
= 480 V IEC
246A-4 2100 5220 170M4410
293A-4 2100 5220 170M5408
365A-4 2100 7830 170M5410
442A-4 2100 9135 170M6410
505A-4 2100 9135 170M6411
585A-4 2100 9135 170M6411
650A-4 2100 10440 170M6412
U
N
= 480 V UL
240A-4 2100 5280 170M4410
302A-4 2100 6525 170M5408
361A-4 2100 7830 170M5410
414A-4 2100 9135 170M6410
477A-4 2100 10440 170M6411
WARNING! The UDC+ and UDC- terminals of the drive
module must not be used for any other than optional external
brake chopper connection.