CHAPTER 8 – OPERATION 134
—
8.7 Stopping the drive
The procedure to stop the drive is described below.
Press the STOP key on the CDP control panel.
The motor stops according to the preset stop
function and the drive stops modulating. While the
motor stops, the status line of the display shows
ReadyRef. The run status message blinks during
the stop sequence.
As long as the stop sequence is in progress, the
drive can always be restarted by pressing the
START key on the CDP control panel.
Just before the motor will come to a standstill, the
CDP control panel displays shortly the message
Stopping.
When the drive has stopped modulating, the CDP
control panel displays ReadyRun.
As long as the MCB has not been opened, the
motor can be started again.
1 L ->
600.0 rpm
StateINU
ReadyRef
MOTOR SP 300.00 rpm
POWER
20.0 kW
1 L ->
600.0 rpm 0
StateINU
Stopping
MOTOR SP 0.00 rpm
POWER
0.0 kW
1 L ->
600.0 rpm 0
StateINU
ReadyRun
MOTOR SP 0.00 rpm
POWER
0.0 kW