39
1SDH000760R0002, L4106
Installation and operating instructions, ATS022
(1
On 1 phase system is not allowed to choose 100 V, 115 V and 120 V.
(2
If voltage level is between 57,7 – 109 Vac, AUX power supply must be used.
(3
In system with rated frequency is 16 2/3 an AUX voltage have to be used; if rated voltage is higher than 100Vac
external voltage transformer must be used.
(4
Whenever ATS022 is used at low temperatures (lower than -10°C) it is advisable to use an external voltage to avoid
any visualization problems on the graphical display.
Table 9.1 Technical Data of ATS022
9. Technical data of the automatic transfer switch
9. Technical data
ATS022 Value
Operating and measuring voltage area on 3 phase
system:
Main voltage 100Vac - 480Vac (±20%)
Phase voltage 57,7Vac - 277Vac (±20%)
AUX voltage 24Vdc - 110Vdc (-10% to 15%)
Frequency 50Hz - 60Hz, 16 2/3 Hz
(3
, 400 Hz (±10%)
Operating and measuring voltage area on 1 phase
system:
Phase voltage 57,7Vac - 240Vac
(1 (2
(±20%)
AUX voltage 24Vdc - 110Vdc
(1
(-10% to 15%)
Frequency 50Hz and 60Hz, 16 2/3 Hz
(3
, 400 Hz (±10%)
Voltage and frequency sensing precision
Voltage 1 %
Frequency 1 %
Relay utilisation category 8 A, AC1, 250 V
Relay utilisation category for connector X26: 6 A, AC1, 250V
Over voltage category III, Uimp 6 kV
IP rating IP20 for the front panel
Temperature area
– 20 to + 60 °C
(4
Transportation and storage temperature – 40 to + 90 °C
Humidity r.h. = 95 % T = 25...55 °C