Start-up 41
Parameter setting examples – ACS355
Speed control using the CiA 402 velocity mode (vl)
This example shows how to configure a speed control application
that uses the velocity mode (vl) of the CiA 402 profile.
When configuring the master, you need to map the following
objects to the transmit and receive PDOs. For an example, see
section Mapping objects required for controlling the drive on
page 66.
The table below gives the recommended drive parameter settings.
CANopen
object
Output data CANopen
object
Input data
0x6040 Control word 0x6041 Status word
0x6042 Target velocity 0x6044 Vl control effort
Drive parameter Setting for ACS355
drives
Description
9802 COMM PROT SEL 4 = EXT FBA Enables communication between
the drive and the fieldbus adapter
module.
5101 FBA TYPE 136 = ETH Pwrlink
1)
Displays the type of the fieldbus
adapter module.
5102 FB PAR 2
(PROFILE)
0 (= CiA 402) Selects the CANopen device
profile CiA 402.
5103 FB PAR 3
(NODE ID)
3
2)
Defines the address of the
device.
3018 COMM FAULT
FUNC
1 = FAULT
2)
Enables fieldbus communication
fault monitoring.
3019 COMM FAULT
TIME
3.0 s
2)
Defines the fieldbus
communication break supervision
time.
5127 FBA PAR
REFRESH
1 = REFRESH Validates the FEPL configuration
parameter settings.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB FEPL-02 Ethernet POWERLINK and is the answer not in the manual?

ABB FEPL-02 Ethernet POWERLINK Specifications

General IconGeneral
BrandABB
ModelFEPL-02 Ethernet POWERLINK
CategoryAdapter
LanguageEnglish

Related product manuals