EasyManuals Logo
Home>ABB>Controller>MS116

ABB MS116 User Manual

ABB MS116
15 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
5
5
Manual motor
protectors
5.6 Low Voltage Products & Systems
AC 1000 - 11/03 ABB Inc. • 888-385-1221 • www.abb-control.com
Short-circuit protection MS 116 Setting ranges, short-circuit strength and max. back-up fuses
Maximum rated current of the short-circuit fuses if I
cc
>I
cs
at at at at at
from to 230 V AC 400 V AC 440 V AC 500 V AC 690 VAC
I
cu
I
cs
gL, gG I
cu
I
cs
gL, gG I
cu
I
cs
gL, gG I
cu
I
cs
gL, gG I
cu
I
cs
gL, gG
A A kA kA A kA kA A kA kA A kA kA A kA kA A
Setting ranges 0.1 ... 0.16
to
1.0 ... 1.6
1.6 ... 2.5 10 10 25 10 10 25 5 5 25
2.5 ... 4.0 6 6 25 6 6 25 2 2 25
4.0 ... 6.3 6 6 63 6 6 63 2 2 40
6.3 ... 10.0 6 6 63 6 6 63 2 2 50
8.0 ... 12.0 25 25 80 25 25 80 6 6 63 6 6 63 2 2 50
10.0 ... 16.0 16 16 80 16 16 80 4 4 63 4 4 63 2 2 63
Short-circuit proof
up to I
cc
=50kA
Short-circuit proof
up to I
cc
=30kA
Type MS116
Technical data
Softstarter type MS116
Standards, approvals UL, CSA, CE
Rated operating current A 16
Current range A 0.16 – 16
Number of poles 3
Frequency Hz 50 / 60
Tripping class A 10
Max. kAIC & 600V kAIC 30
Mechanical life Operations 100,000
Wire range AWG 12 – 18
Terminal torque in. lbs. 14
Terminal tool options Flat screwdriver PZ2
Permissible attitude without derating m 3000
Degree of protection IP20
UL Listed for group installation Yes
Self-protected Type E manual
combination starter No
Accessories
Terminal shroud No
Auxiliary contacts Yes
Shunt trip No
Trip signal contacts Yes
UV release Yes
Busbar Yes
Through the door handle Yes
Minimum enclosure size H x W x D
Loads for accessories
Auxiliary contact for front mounting, HKF AC15 24 V, 3.0 A
230 V, 1.5 A
Auxiliary contact for front mounting, HKF DC13 24 V, 1.0 A
48 / 60V, 0.7 A
110 V, 0.27 A
Auxiliary and signal contact, HK + SK AC15 24 V, 6 A
230 V, 4 A
400 V, 3 A
Auxiliary and signal contact, HK + SK DC13 24 V, 2 A
110 V, 0.5 A
220 V, 0.25 A
440 V, 0.1 A
Electromagnet trips
Response value set ex-works 9.6 – 14.4 x In
Undervoltage release
Pick-up value % of U C 85
Drop-out value % of U C 35 – 75
Power consumption
Pick-up VA Consult factory
Hold VA Consult factory

Other manuals for ABB MS116

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB MS116 and is the answer not in the manual?

ABB MS116 Specifications

General IconGeneral
BrandABB
ModelMS116
CategoryController
LanguageEnglish

Related product manuals