Displays the output data of the VSGGIO function.
11.6.8.3 IEC61850 generic communication I/O functions DPGGIO
Main menu/Test/Function status/Control/DoubelPointIndication(DPGGIO)/
DP
Displays the output data of the DPGGIO function.
11.6.8.4 Synchrocheck and energizing check SESRSYN
Main menu/Test/Function status/Control/Synchronizing(RSYN,25)/SYN
Displays available instances of SESRSYN with a number of measurements per
instance. These include information about which lines and buses selected, various
voltage and frequency differences and feedback on synchronization status.
11.6.9 Monitoring
Monitoring includes large amounts of viewable data including Disturbance report
data, Service values, Current phasors, Voltage phasors, Milliampere signal level
supervision, Binary signal status report, Events, MVGGIO, MVExpander and LEDs.
11.6.9.1 Logical signal status report BINSTATREP
Main menu/Test/Function status/Monitoring/BinarySignalStatusReport/SSR
Displays sets of output measurements with several outputs per set of measurements.
11.6.9.2 Disturbance report DRPRDRE
Test/Function status/Monitoring/DisturbanceReport(RDRE)
Displays data about disturbance reports. The disturbance report can be switched
off, a disturbance report that has been initiated is indicated by a boolean number, as
are completed reports and cleared reports. The parameter MEM USED indicates
that more than 80% of the memory space available for disturbance report data has
been used and the need to clear the memory is pressing. The Memory USED
parameter generates an integer value showing the actual amount of memory used
by the disturbance record repository. The maximum number of incoming analog
channels is 40 and their Trig status is indicated here. The Fault number parameter
generates an integer indicating the number of faults recorded since the last clearing
of the memory.
11.6.9.3 Event counter CNTGGIO
Main menu/Test/Function status/Monitoring/EventCounter(GGIO)/CNT
1MRK 502 014-UEN C Section 11
Test the IED
75
Operator's manual

Table of Contents

Other manuals for ABB REG670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB REG670 and is the answer not in the manual?

ABB REG670 Specifications

General IconGeneral
BrandABB
ModelREG670
CategoryProtection Device
LanguageEnglish

Related product manuals