Section 2 1MAC302441-MB A
IEC 60870-5-101/104 data mappings
12 RER620
Point List Manual
2.2 Point list for RER620 Ver. 1.0
Table 2: Analog values
No events 61850 Path IOA Disabled Description Multiplier Interrogation
CMMXU1.A.phsA.cVal.mag.f 8000 "IA,IB,IC:phase A amplitude" Yes
CMMXU1.A.phsA.instCVal.ang.f 8001 "IA,IB,IC:phase A angle" Yes
CMMXU1.A.phsB.cVal.mag.f 8003 "IA,IB,IC:phase B amplitude" Yes
CMMXU1.A.phsB.instCVal.ang.f 8004 "IA,IB,IC:phase B angle" Yes
CMMXU1.A.phsC.cVal.mag.f 8006 "IA,IB,IC:phase C amplitude" Yes
CMMXU1.A.phsC.instCVal.ang.f 8007 "IA,IB,IC:phase C angle" Yes
CSMSQI1.SeqA.c1.cVal.mag.f 8012 "I1,I2,I0:amplitude" Yes
CSMSQI1.SeqA.c1.instCVal.ang.f 8013 "I1,I2,I0:angle" Yes
CSMSQI1.SeqA.c2.cVal.mag.f 8015 "I1,I2,I0:amplitude" Yes
CSMSQI1.SeqA.c2.instCVal.ang.f 8016 "I1,I2,I0:angle" Yes
CSMSQI1.SeqA.c3.cVal.mag.f 8018 "I1,I2,I0:amplitude" Yes
CSMSQI1.SeqA.c3.instCVal.ang.f 8019 "I1,I2,I0:angle" Yes
FLTMSTA1.OpCnt.stVal 8024 FLTMSTA1:OpCnt status Yes
FMMXU1.Hz.mag.f 8025 f:Hz magnitude Yes
FRPTRC1.StrDur.mag.f 8026 Freq1:StrDur magnitude Yes
FRPTRC2.StrDur.mag.f 8027 Freq2:StrDur magnitude Yes
PEMMXU1.TotPF.mag.f 8032 "P,E:TotPF magnitude" Yes
PEMMXU1.TotW.mag.f 8033 "P,E:TotW magnitude" Yes
PEMMXU1.TotVA.mag.f 8034 "P,E:TotVA magnitude" Yes
PEMMXU1.TotVAr.mag.f 8035 "P,E:TotVAr magnitude" Yes
RESCMMXU1.A.res.cVal.mag.f 8036 IG:amplitude Yes
RESCMMXU1.A.res.instCVal.ang.f 8037 IG:angle Yes
SDARREC1.OpCnt1.stVal 8041 79:OpCnt1 status Yes
SDARREC1.OpCnt2.stVal 8042 79:OpCnt2 status Yes
SDARREC1.OpCnt3.stVal 8043 79:OpCnt3 status Yes
SDARREC1.OpCnt4.stVal 8044 79:OpCnt4 status Yes
SDARREC1.OpCnt5.stVal 8045 79:OpCnt5 status Yes
VMMXU1.PhV.phsA.cVal.ang.f 8046 "VA,VB,VC:phase A angle" Yes
VMMXU1.PhV.phsA.cVal.mag.f 8047 "VA,VB,VC:phase A amplitude" Yes
VMMXU1.PhV.phsB.cVal.ang.f 8048 "VA,VB,VC:phase B angle" Yes
VMMXU1.PhV.phsB.cVal.mag.f 8049 "VA,VB,VC:phase B amplitude" Yes
VMMXU1.PhV.phsC.cVal.ang.f 8050 "VA,VB,VC:phase C angle" Yes
VMMXU1.PhV.phsC.cVal.mag.f 8051 "VA,VB,VC:phase C amplitude" Yes
VMMXU1.PPV.phsAB.cVal.mag.f 8052 "VA,VB,VC:phase AB amplitude" Yes
VMMXU1.PPV.phsAB.instCVal.ang.f 8053 "VA,VB,VC:phase AB angle" Yes
VMMXU1.PPV.phsBC.cVal.mag.f 8055 "VA,VB,VC:phase BC amplitude" Yes
VMMXU1.PPV.phsBC.instCVal.ang.f 8056 "VA,VB,VC:phase BC angle" Yes