EasyManuals Logo

ABB S900 User Manual

ABB S900
48 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #33 background imageLoading...
Page #33 background image
I/O System S900
Communication Interface for PROFIBUS DP, CI920
3BDD010422R0101 33
the PROFIBUS communication of the active CI920 fails longer than 15 s.
This operating mode features the following restriction:
No diagnostics of the redundant PROFIBUS line.
Redundancy Mode "1"
In redundancy operating mode LR_MODE1 a certain behavior of the master
is assumed, in order to be able to diagnose all failures of the PROFIBUS
lines. The redundant CI920 becomes active when
the active CI920 is removed, or
the PROFIBUS communication of the active CI920 fails.
This redundancy operating mode features the following characteristics:
Monitoring the active PROFIBUS connection in transmit and receive
direction
Diagnosing the redundant PROFIBUS connection in transmit and receive
direction
No additional engineering requirements,
No additional bus load.
Prerequisites
The CI920 must be parameterized accordingly for redundancy.
The address of the passive CI920 must be a vacant node address.
The PROFIBUS master must poll the passive CI920 (FDL status polling).
Alternatively a minimum configuration can be set up for each passive
CI920. This is optional and facilitates the diagnostics in the control
system. The configuration is limited to a CI920 user data (CIPB C), so
that the bus load does not increase drastically.
Both PROFIBUS lines must be sufficiently isolated.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB S900 and is the answer not in the manual?

ABB S900 Specifications

General IconGeneral
BrandABB
ModelS900
CategoryI/O Systems
LanguageEnglish

Related product manuals