25
10. Application of the X-ray emission Standards
One of the physical properties of vacuum insulation is the possibility of
X-ray emission when the interrupter contacts are open.
The specific tests carried out at the PTB laboratories (Physikalisch-
Technische Bundesanstalt, in Brunswick - Germany) show that local
emission at a distance of 10 cm from the interrupter or pole surface,
does not exceed 1 mSv/h.
It follows that:
at the rated service voltage the use of vacuum interrupters is abso-
lutely safe;
application of the withstand voltage at power frequency, according to
the IEC 62271-100 and VDE 0670 Standards, is safe;
application of a voltage higher than the withstand voltage at power
frequency or of a test voltage in direct current, specified in the IEC
and VDE Standards, cannot be used;
limitation of the above-mentioned local phenomena, with interrupters
with open contacts, depends on keeping the specific distance be-
tween the contacts.
This condition is intrinsically guaranteed by correct operation of the
operating mechanism and by the adjustments of the transmission sys-
tem.
11. Spare parts and accessories
All assembly operations of spare parts/accessories must
be carried out following the instructions enclosed with
the spare parts, by ABB personnel or by suitably qualified
customer personnel with in-depth knowledge of the ap-
paratus (IEC 60694) and of all the Standards aimed at car-
rying out these interventions in safe conditions. Should
the maintenance be carried out by the customer’s person-
nel, responsibility for the interventions remains with the
customer. Before carrying out any operation, always make
sure that the circuit-breaker is open, the springs discharged
and that it is not energised (medium voltage circuit and
auxiliary circuits).
To order circuit-breaker spare parts/accessories, refer to the ordering
sales codes indicated in the technical catalogue and always state the
following:
type of circuit-breaker
rated voltage of the circuit-breaker
rated normal current of the circuit-breaker
breaking capacity of the circuit-breaker
serial number of the circuit-breaker
rated voltage of any electrical spare parts.
For availability and to order spare parts, please contact our Service
office.
11.1. List of spare parts
Shunt opening release
Additional shunt opening release
Undervoltage release
Contact for signalling undervoltage release energised/de-energised
Time delay device for undervoltage release
Mechanical override for undervoltage release
Shunt closing release
Spring charging geared motor with electrical signalling of springs
charged
Geared motor thermomagnetic protection circuit-breaker
Contact for signalling geared motor protection circuit-breaker open/
closed
Contact for signalling closing springs charged/discharged
Circuit-breaker auxiliary contacts
Opening solenoid
Key lock in open position
Opening pushbutton protection
Closing pushbutton protection
Set of six main isolating contacts
Current sensors
PR521 protection releases
Connector complete with sheath
Wheel Kit
Operation counter
Complete pole.