100
AWM-G-2009 Electrical Data
Electrical Data
Electrical Data - Cooling Only (R22)
MODEL
INDOOR UNIT AWM 07G AWM 09G
OUTDOOR UNIT ALC 07C ALC 09C
INDOOR MOTOR
INSULATION GRADE CLASS E CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 23 24
RATED RUNNING CURRENT A 0.11 0.11
MOTOR OUTPUT W 88
POLES 44
OUTDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 41 45
RATED RUNNING CURRENT A 0.19 0.20
MOTOR OUTPUT W 20 20
POLES 66
COMPRESSOR
INSULATION GRADE CLASS E CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR mF 20.0 30.0
RATED INPUT POWER W 526 850
RATED RUNNING CURRENT A 2.45 3.80
LOCKED ROTOR AMP. A 11.3 18
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
Electrical Data - Heat Pump (R22)
MODEL
INDOOR UNIT AWM 09GR AWM 10GR
OUTDOOR UNIT ALC 09CR ALC 10CR
INDOOR MOTOR
INSULATION GRADE CLASS E CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 24 26
RATED RUNNING CURRENT A 0.11 0.11
MOTOR OUTPUT W 89
POLES 44
OUTDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 40 52
RATED RUNNING CURRENT A 0.18 0.23
MOTOR OUTPUT W 20 35
POLES 66
COMPRESSOR
INSULATION GRADE CLASS E CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR mF 25.0 30.0
RATED INPUT POWER (COOLING) W 846 759
RATED INPUT POWER (HEATING) W 686 679
RATED RUNNING CURRENT (COOLING) A 3.70 3.40
RATED RUNNING CURRENT (HEATING) A 3.10 3.00
LOCKED ROTOR AMP. A 18 19
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.