EasyManuals Logo
Home>Acson>Air Conditioner>AWM 20G

Acson AWM 20G Technical Manual

Acson AWM 20G
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #105 background imageLoading...
Page #105 background image
102
AWM-G-2009 Electrical Data
Electrical Data - Cooling Only (R22)
MODEL
INDOOR UNIT AWM 20G AWM 20G
OUTDOOR UNIT ALC 18C ALC 20C
INDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 47 47
RATED RUNNING CURRENT A 0.22 0.22
MOTOR OUTPUT W 20 20
POLES 44
OUTDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 120 120
RATED RUNNING CURRENT A 0.53 0.53
MOTOR OUTPUT W 64 64
POLES 66
COMPRESSOR
INSULATION GRADE CLASS E CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR mF 60.0 60.0
RATED INPUT POWER W 1643 1640
RATED RUNNING CURRENT A 7.37 7.20
LOCKED ROTOR AMP. A 32 32
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.
Electrical Data - Heat Pump (R22)
MODEL
INDOOR UNIT AWM 20GR AWM 25GR
OUTDOOR UNIT ALC 20CR ALC 25CR
INDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 47 66
RATED RUNNING CURRENT A 0.22 0.29
MOTOR OUTPUT W 20 25
POLES 44
OUTDOOR MOTOR
INSULATION GRADE CLASS B CLASS B
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
RATED INPUT POWER W 120 124
RATED RUNNING CURRENT A 0.53 0.54
MOTOR OUTPUT W 75 75
POLES 66
COMPRESSOR
INSULATION GRADE CLASS E CLASS E
POWER SOURCE V/Ph/Hz 220 - 240 / 1 / 50 220 - 240 / 1 / 50
CAPACITOR mF 60.0 50.0
RATED INPUT POWER (COOLING) W 1640 2340
RATED INPUT POWER (HEATING) W 1590 2260
RATED RUNNING CURRENT (COOLING) A 7.20 10.49
RATED RUNNING CURRENT (HEATING) A 7.00 10.24
LOCKED ROTOR AMP. A 32 54
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
2) ALL UNITS ARE BEING TESTED AND COMPLY TO ISO 5151.