AWM-G-2009 Service and Maintenance
Pre Start Up Maintenance
(After Extended Shutdown)
Inspect thoroughly and clean indoor and outdoor units.
Clean or replace air lters.
Clean condensates drain line.
Clean clogged indoor and outdoor coils.
Check fan imbalance before operation.
Tighten all wiring connections and panels.
Check for refrigerant leakage.
Outdoor Models
The design of the ALC outdoor series allows servicing to be carried out readily and easily. The removal of the
top/front and back panel make almost every part accessible.
Under normal circumstances, these outdoor units only require a check and cleaning of air intake coil surface
once quarterly. However, if a unit is installed in areas subjected to much oil mist and dust, the coils must be
regularly cleaned by quali ed Air Conditioner Service Technicians to ensure suf cient heat exchange and
proper operation. Otherwise, the systems life span may be shortened.
Caution
Do not charge OXYGEN, ACETYLENE OR OTHER FLAMMABLE and poisonous gases into the unit when
performing a leakage test or an airtight test. These gases could cause severe explosion and damage if exposed to
high temperature and pressure. It is recommended that only nitrogen or refrigerant be charged when performing the
leakage or airtight test.