EasyManuals Logo
Home>Acson>Air Conditioner>AWM 20G

Acson AWM 20G Technical Manual

Acson AWM 20G
167 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #72 background imageLoading...
Page #72 background image
69
Performance Data AWM-G-2009
2
nd
Step:
To obtain the Total capacity and Sensible capacity for
(a) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 35°C DB
Indoor DB˚C Indoor WB˚C
Outdoor DB, ˚C
35
TC (kW) SC (kW)
........
........
20 15
...........................................
2.558 1.403
23 15
x
3
y
3
24 15 2.558 1.990
Total capacity, TC
x
3
= 2.558kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 35°C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
24º C – 20º C
=
1.990kW – 1.181kW
24º C – 23º C 1.990kW – y
3
y
1
= 1.844kW
(b) Indoor Condition: 23°C DB, 15°C WB
Outdoor Condition: 40°C DB
Indoor DB˚C Indoor WB˚C
Outdoor DB, ˚C
40
TC (kW) SC (kW)
........
........
20 15
...........................................
2.355 1.215
23 15
x
4
y
4
24 15 2.355 1.802
Total capacity, TC
x
4
= 2.355kW (Same as Total capacity at 20°C Indoor DB / 15°C Indoor WB & 40°C Outdoor WB)*
Sensible capacity, SC
Interpolation Method:
24º C – 20º C
=
1.597kW – 0.963kW
24º C – 23º C 1.597kW – y
4
y
2
= 1.655kW
* This is due to 2 different conditions with same WB temperature, will have the same level of enthalpy. For more
details, please refer to psychrometrics chart

Other manuals for Acson AWM 20G

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Acson AWM 20G and is the answer not in the manual?

Acson AWM 20G Specifications

General IconGeneral
BrandAcson
ModelAWM 20G
CategoryAir Conditioner
LanguageEnglish

Related product manuals