A hazard of personal injury from automatic restart exists
with 2-wire control. 2-wire control uses maintained Run
contacts that act as both Run (closed) and Stop (open)
devices. Opening the Stop contact (terminal 20) will stop
the drive. If this contact is reclosed, any fault will be reset.
If a valid Start command is still present, the drive will
restart. Only use 2-wire control for applications outlined in
NFPA79, "Under Voltage Protection."
If a 3-wire device (i.e. HIM) is also used, pressing the HIM
Stop key will also stop the drive. Releasing the Stop key
will clear any faults that are present, but the drive will not
restart without cycling the Start contact.
Input 1
Input 2
Common
Input 3
Input 4
Input 5
Common
Input 6
Input 7
Input 8
Common
Input 9
Encoder B
Encoder NOT A
Encoder NOT B
Encoder A
+12V (200mA max.)
Encoder Common
31
32
33
34
35
36
Included on
L4E through L9E
Only
to TE
Recommended Cable (or equivalent):
Belden 9730 for distances less than 30 meters (98 feet)
Belden 9773 for distances greater than 30 meters (98 feet)
Differential Encoder Output
Connections Shown
Refer to User Manual
for
Single-Ended Connections
1
See
Speed Select
Table.
2
If this mode is selected, the status of all inputs can
be read at the [Input Status] parameter. However,
only “Stop/Fault Reset” and “Enable” will have
control function.
3
These inputs must be present (reprogram if
necessary) before drive will start.
4
Bit 0 of [Direction Mask] must = 1 to allow TB3
direction change/bipolar operation.
Speed Select Input State vs. Frequency Source
Speed Select 3 Speed Select 2 Speed Select 1 Frequency Source
Open Open Open [Freq Select 1]
Open Open Closed [Freq Select 2]
Accessed through [Freq Select 2] parameter [Preset Freq 1]
Open Closed Open [Preset Freq 2]
Open Closed Closed [Preset Freq 3]
Closed Open Open [Preset Freq 4]
Closed Open Closed [Preset Freq 5]
Closed Closed Open [Preset Freq 6]
Closed Closed Closed [Preset Freq 7]
Important: The final speed command may be affected by the type of
modulation selected with [Speed Control], parameter 77.
Refer to [Speed Control] in Chapter 6 of the User Manual for
further information.
Input Mode (Start/Stop Functions Only)
Status
2
(Factory Default)
Status
Stop/Fault Reset
3
2-Wire Control
Single-Source Control
Run Forward
Stop/Fault Reset
3
3-Wire Control
Single-Source Reversing
Start
Stop/Fault Reset
3
Common
Rev/For
4
(Programmable)
Factory Default Inputs
Jog (Programmable)
Auxiliary
3
(Programmable)
Common
Speed Select 3
1
(Programmable)
Speed Select 2
1
(Programmable)
Speed Select 1
1
(Programmable)
Common
Enable
3
(Not Programmable) Enable
3
Status Only
Default Mode
shown at right
is not active
when
[Input Mode]
is set to "Status"